1.7.2. Installation notes
This control panel has been designed to comply with the EN54 standard, so it must be
installed in accordance with the requirements of that standard.
⚠
WARNING!:
Failing to meet these requirements may cause
a system malfunction and constitute a breach of the EN54
standard.
CERTIFIED INSTALLER:
Make sure that the person installing the panel is a certified
installer. It is also essential that the system of which this control panel is part has been
designed by qualified staff and complies with the UNE 23007-14 standard, any municipal
by-laws and any regulations in force in the place where the control panel is being installed.
1.7.3. Operating conditions
Before installing the CAD-020/040 series control panel, you must check that a number
of conditions are met:
⚠
WARNING!:
Do not install the control panel if any of the
following conditions are not met.
•
The ambient temperature must be between -5ºC and 40ºC.
•
The relative humidity must be between 5% and 95%, non-condensing.
•
The control panel must be installed in a place where it is not subjected to vibrations.
•
The control panel's controls must be accessible.
•
The control panel must be properly earthed. The control panel may operate incorrectly
or be damaged if it is subjected to induced transient electrical discharges.
•
The wall on which the control panel is installed must be sufficiently flat, to avoid any
deformation of the case and subsequent problems with closing it.
•
Do not install the control panel in a place where it is difficult to access it or its
connections.
NOTE:
The CAD-020/040 series control panel is certified to
operate under certain conditions; exceeding the operating ranges
of the control panel may result in the warranty being voided.