Blast chiller Service Manual
27
Rev 07/04/2015
Parameter Description
Factory Value
P64
temperature below which the minimum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7
+ P64" (with reference to the cabinet probe)
0 = no alarm
0
P65
temperature above which the maximum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7
+ P65" (with reference to the cabinet probe)
0 = no alarm
0
P66
temperature below which the minimum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e.
"P8 + P66" (with reference to the cabinet probe)
0 = no alarm
0
P67
temperature above which the maximum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e.
"P8 + P67" (with reference to the cabinet probe)
0 = no alarm
0
P68
P64, P65, P66 and P67 differential
2
P69
storage operation start-up temperature alarm delay
0
P70
temperature alarm delay
0
P71
enable printing
1 = YES
0
P72
print interval
5
P73
HACCP alarm list deletion
1 = YES
0
P74
Baudrate
0=2400
1=4800
2=9600
3=19200
2
P75
Bit polarity
0=no polarity
1=even
2=odd
2
P76
Board address
1
Summary of Contents for GBC-15
Page 1: ...Service Manual Blast Chiller...
Page 2: ...Rev 07 04 2015 2...
Page 3: ...Blast chiller Service Manual 3 Rev 07 04 2015...
Page 32: ...Rev 07 04 2015 32...
Page 40: ...Rev 07 04 2015 40...
Page 50: ...Rev 07 04 2015 10 20 10 0 10 20 30 40 kOhms C kOhmsVsTempChart NTC 10kOhms 25 C ZOOM...
Page 57: ...Blast chiller Service Manual 17 Rev 07 04 2015 L1 L2...
Page 91: ...Blast chiller Service Manual 51 Rev 07 04 2015 6 SCHEMATICS 6 1 SCHEME OF COMPONENTS...
Page 97: ...Blast chiller Service Manual 57 Rev 07 04 2015...
Page 100: ...Rev 07 04 2015 60...