INSPECTING HEATER

BURNER PRIMARY AIR HOLES

Air is drawn into the burner through the holes 
in  the  fitting  at  the  burner  entrance.  These 
holes may become blocked with dust or lint. 
Periodically inspect these holes for any block-
age and clean if needed. Blocked air holes 
will create soot.

MAIN BURNER

Periodically inspect all burner flame holes with 
the  heater  running. All  slotted  burner  flame 
holes should be open with yellow flame pres-
ent. All round burner flame holes should be 
open with a small blue flame present. Some 
burner flame holes may become blocked by 
debris  or  rust,  with  no  flame  present.  If  so, 
turn off heater and let cool. Remove blockage, 
blocked burner flame holes will create soot.

Pilot Burner

Thermocouple

Figure 38 - Correct Pilot Flame Pattern 

(Your pilot may vary from pilots shown)

Pilot Burner

Thermocouple

Figure 39 - Incorrect Pilot Flame Pattern 

(Your pilot may vary from pilots shown)

CLEANING AND MAINTENANCE

Check  pilot  flame  pattern  and  burner flame 
patterns often.

PILOT FLAME PATTERN

Figure 38 shows a correct pilot flame pattern. 
Figure 39 shows an incorrect pilot flame pat-
tern. The incorrect pilot flame is not touching 
the thermocouple. This will cause the thermo-
couple to cool. When the thermocouple cools, 
the heater will shut down.
If  pilot  flame  pattern  is  incorrect,  as  shown 
in Figure 39
•  turn  heater  off  (see 

To  Turn  Off  Gas  to 

Appliance

, page 19)

•  see 

Troubleshooting

, page 24

Note: The pilot flame on natural gas units will 
have a slight curve, but flame should be blue 

and have no yellow or orange color.

  WARNING:  Turn  off  heater 

and let cool before cleaning.

  CAUTION:  You  must  keep 

control  areas,  burners,  and 

circulating  air  passageways 

of  heater  clean.  Inspect  these 

areas of heater before each use. 

Have  heater  inspected  yearly 

by  a  qualified  service  person. 

Heater may need more frequent 

cleaning  due  to  excessive  lint 

from carpeting, pet hair, bedding 

material, etc.

  WARNING:  Failure  to  keep 

the  primary  air  opening(s)  of 

the burner(s) clean may result in 

sooting and property damage.

BURNER INjECTOR HOLDER AND 
PILOT AIR INLET HOLE

The primary air inlet holes allow the proper 
amount of air to mix with the gas. This pro-
vides  a  clean  burning  flame.  Keep  these 
holes  clear  of  dust,  dirt,  lint,  and  pet  hair. 
Clean  these  air  inlet  holes  prior  to  each 
heating season. Blocked air holes will create 
soot. We recommend that you clean the unit 
every  three  months  during  operation  and 
have heater inspected yearly by a qualified 
service person.
We also recommend that you keep the burner 
tube and pilot assembly clean and free of dust 
and dirt. To clean these parts we recommend 
using compressed air no greater than 30 PSI. 
Your local computer store, hardware store, or 
home center may carry compressed air in a 
can. If using compressed air in a can, please 
follow the directions on the can. If you don't 
follow directions on the can, you could dam-
age the pilot assembly.
1.  Remove control cover log and front log.

Summary of Contents for LDL3930NRB

Page 1: ...ctrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire depa...

Page 2: ...ented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation s...

Page 3: ...ings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert h...

Page 4: ...nd Maintenance page 22 9 Before using furniture polish wax carpet cleaner or similar products turn heater off If heated the vapors from these products may create a white powder residue within burner b...

Page 5: ...DS pilot shuts off the heater if there is not enough fresh air Piezo Ignition System This heater has a piezo ignitor This system requires no matches batteries or other sources to light heater Air For...

Page 6: ...Z223 1 NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1 000 Btu hr 4 8 m3 per kw of the aggregate input rating of all appliances installed in that space and a...

Page 7: ...Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined space you must provide two permanent openings one within 12 of the ce...

Page 8: ...e is equipped for either natural gas or propane LP gas but not both Gas type is indicated on the rat ingplate Fieldconversionisnot permitted NOTICE Thisheater isintended for use as supplemental heat U...

Page 9: ...ee Operation WARNING Maintain the minimum clearances If you can provide greater clearances from floor ceiling and adjoin ing wall MINIMUM FIREPLACE CLEARANCE TO COMBUSTIBLE MATERIALS Side Wall 16 Ceil...

Page 10: ...es you must operate heater with chimney flue damper open Go to Install ing Damper Clamp Accessory for Vented Operation page 11 Mantel Clearances In addition to meeting noncombustible mate rial clearan...

Page 11: ...must be installed only in a solid fuel burning fireplace with a working flue and constructed of noncombustible material ForMassachusettsResidentsOnly Installation ofthisventedgaslogsetintheCommonwealt...

Page 12: ...oved flexible gas hose to gas control fitting in heater see Figure 11 IMPORTANT Hold gas fitting with wrench when connecting flexible gas hose 2 Locate two masonry screws in hardware package 3 Place h...

Page 13: ...must supply an external regulator The external regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 of water If you do not re duce incoming gas pressu...

Page 14: ...tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 17 IMPORTANT Install equipment shutoff valve in an accessible location The equipment shutoff valve is for turni...

Page 15: ...as valve located on or near gas meter for natural gas or using compressed air 4 Check all joints of gas supply piping system Apply noncorrosive leak detection fluid to all joints Bubbles forming show...

Page 16: ...ifically approved with this heater may result in property damage or personal injury CAUTION After installa tion and periodically thereafter check to ensure that no flame comes in contact with any log...

Page 17: ...hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air an...

Page 18: ...fter the pilot is lit 1 STOP Read the safety information on page 17 2 Make sure equipment shutoff valve is fully open 3 Remove control cover log see Figure 26 4 Set remote selector switch in the REMOT...

Page 19: ...its will have a slight curve but flame should be blue and have no yellow or orange color Figure 28 Pilot Propane LP Ignitor Electrode Pilot Burner Figure 29 Pilot Natural Ignitor Electrode Pilot Burne...

Page 20: ...in high position see Figure 32 A beep from the receiver confirms the command Push ON OFF button again and burners will turn off A beep from the receiver confirms the command Figure 32 Hand Held Remot...

Page 21: ...re The control system will cycle the fireplace on or off to maintain se lected temperature Child Safety Lock Out This function lets you deactivate the remote control buttons It is active when the lock...

Page 22: ...o Turn Off Gas to Appliance page 19 see Troubleshooting page 24 Note The pilot flame on natural gas units will have a slight curve but flame should be blue and have no yellow or orange color WARNING T...

Page 23: ...y Air Inlet Holes Shape of Holes May Vary by Model Figure 40 Injector Holder On Outlet Burner Tube Figure 41 Pilot Inlet Air Hole LOGS If you remove logs for cleaning refer to In stalling Logs page 16...

Page 24: ...n in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubin...

Page 25: ...l knob pressed in 30 seconds 3 Wait one minute for safety interlock system to reset Repeat ignition operation 4 Fully open equipment shut off valve 5 A Contact local natural or propane LP gas company...

Page 26: ...r off when us ing furniture polish wax carpet cleaners or similar products 1 Refer to Air for Combustion and Ventilation require ments page 5 1 Properly locate logs see Installing Logs page 16 2 Elimi...

Page 27: ...fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warn ing statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burne...

Page 28: ...nt parts This will protect your warranty coverage for parts replaced under warranty Parts Under Warranty Contact authorized dealers of this product If they can t supply original replacement part s cal...

Page 29: ...onal rock is desired CLEANING KIT CCK For all models Your vent free gas appliance requires regular cleaning and maintenance to prevent performance problems This kit gives you the tools and instruction...

Page 30: ...atech com 121486 01F 30 Parts Models LDL3930NRB and LDL3930PRB 11 28 2 3 25 18 5 19 10 7 7 6 4 20 24 16 14 26 9 23 23 15 16 8 23 23 23 23 17 22 28 29 21 1 12 13 27 1 27 2 27 3 27 4 27 5 27 6 27 7 27 8...

Page 31: ...Extension 1 21 121129 01 Proflame Remote Control 1 22 121129 02 Proflame Receiver 1 23 M11084 26 Screw HWH AB 10 16 x 0 38 17 24 M12461 26 Screw Hex SLT WSR 10 32 x 0 38 6 25 098249 01 ODS Nut 2 26 1...

Page 32: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Reviews: