7

  CAUTION:  Use  only  new, 

black  iron  or  steel  pipe.  Inter-

nally-tinned copper tubing may 

be used in certain areas. Check 

your  local  codes.  Use  pipe  of 

1/2" diameter or greater to allow 

proper gas volume to log set. If 

pipe is too small, undue loss of 

volume will occur.

Installation  must  include  a  equipment  shutoff 

valve, union, and plugged 1/8" NPT tap. Locate 

NPT  tap  within  reach  for  test  gauge  hook  up. 

NPT  tap  must  be  upstream  from  log  set  (see 

Figure 4).

IMPORTANT:

 Install equipment shutoff valve 

in an accessible location. The equipment shutoff 

valve is for turning on or shutting off the gas to 

the appliance.

INSTALLATION

Continued 

Figure 4 - Gas Connection

*  Purchase  the  optional  CSA  design-certified 

equipment shutoff valve from your dealer. See 

Accessories

, page 18.

** Minimum inlet pressure for purpose of input 

adjustment.

Apply  pipe  joint  sealant  lightly  to  male  NPT 

threads. This  will  prevent  excess  sealant  from 

going into pipe. Excess sealant in pipe could result 

in a clogged burner injector.

  WARNING:  Use  pipe  joint 

sealant that is resistant to liquid 

petroleum (LP) gas. 

We recommend that you install a sediment trap in 

supply line as shown in Figure 4. Locate sediment 

trap where it is within reach for cleaning. Install in 

piping system between fuel supply and appliance. 

Locate sediment trap where trapped matter is not 

likely to freeze. A sediment trap traps moisture and 

contaminants. This keeps them from going into log 

set controls. If sediment trap is not installed or is 

installed wrong, log set may not run properly.

CHECKING GAS CONNECTIONS

 WARNING: Test all gas piping 

and  connections,  internal  and 

external to unit, for leaks after 

installing or servicing. Correct 

all leaks at once.

 WARNING: Never use an open 

flame to check for a leak. Apply 

a  noncorrosive  leak  detection 

fluid to all joints. Bubbles form-

ing show a leak. Correct all leaks 

at once.

PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM 
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)

1.  Disconnect log set and its individual equipment 

shutoff valve from gas supply piping system. 

2.  Cap off open end of gas pipe where equipment 

shutoff valve was connected.

3.  Pressurize supply piping system by either us-

ing compressed air or opening main gas valve 

located on or near gas meter.

4.  Check all joints of gas supply piping system. 

Apply noncorrosive leak detection fluid to gas 

joints. Bubbles forming show a leak. 

5.  Correct all leaks at once.
6.  Reconnect  log  set  and  equipment  shutoff 

valve to gas supply. Check reconnected fit-

tings for leaks.

3" Minimum

Sediment Trap

From Gas Meter 
(5" W.C.** to 
10.5" W.C. 
Pressure)

CSA Design-Certified 
Equipment Shutoff Valve 
With 1/8" NPT Tap*

Approved Flexible Gas Hose (if 
allowed by local codes)

Tee Joint

Pipe Nipple

Cap

Summary of Contents for Comfort Glow BRENTWOOD LCF18

Page 1: ...nce WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow th...

Page 2: ...ust be provided Refer to the National Fuel Gas Codes ANSI Z233 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation This appliance may be installed in an aftermarket per manently located manufactu...

Page 3: ...cals known to the State of California to cause cancer or birth defects or other reproductive harm WARNING Keep ue open when operating unit IMPORTANT Read this owner s manual carefully and completely b...

Page 4: ...h the Na tional Fuel Gas Code ANSI Z233 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation 7 Do not run log set where ammable liquids or vapors are used or stored under dusty conditions 8 Do not...

Page 5: ...r this appliance You must use the millivolt valve safety pilot kit to use the wall switch with this appliance See Accessories page 18 INSTALLATION CAUTION Donotremovethe dataplatesattachedtotheburner...

Page 6: ...ht a tightly rolled newspaper on one end and place it at the inside front edge of the replace Observe the smoke and be sure the vent is properly drawing it up the chimney If the smoke spills out into...

Page 7: ...system between fuel supply and appliance Locate sediment trap where trapped matter is not likely to freeze Asediment trap traps moisture and contaminants This keeps them from going into log set contr...

Page 8: ...d see Figure 6 Tighten using a wrench 6 Using burner clamp screw and nut provided assemble clamp to pan U style and triple burners only This will hold the burner mani fold in place 7 If using optional...

Page 9: ...nifold and reaming the ports with a modi ed paper clip or other suitable tool 5 When nished testing turn the gas shutoff valve OFF to extinguish all ames ADDING PAN MATERIAL 1 Open the bag of ash bed...

Page 10: ...call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the re department LIGHTING INSTRUCTIONS 1 STOP Read the safety informa...

Page 11: ...this log set for the rst time after hooking up to gas sup ply If so the control knob may need to be pressed in for 30 seconds This will allow air to bleed from the gas system If control knob does not...

Page 12: ...ave your model and serial numbers of your appliance ready You can also visit DESA s technical services web site at www desatech com REPLACEMENT PARTS Note Use only original replacement parts This will...

Page 13: ...sets to produce moderate levels of carbon soot where ames contact the logs Burner is excessively noisy Note The movement and com bustion of gas will create low unavoidable levels of noise Burner ame...

Page 14: ...ROBLEM When ignitor button is pressed there is spark at pilot but no igni tion GA9050A Only Pilot lights but ame goes out when control knob is released GA9050A Only Burner does not light after pilot i...

Page 15: ...ce person 1 Open ue to maximum Stop using odor causing products while log set is running 2 Locate and correct all leaks see Checking Gas Connec tions page 7 1 Locate and correct all leaks see Checking...

Page 16: ...www desatech com 115043 01C 16 ILLUSTRATED PARTS BREAKDOWN MODELS LCF18 AND LCF24 3 13 1 8 6 4 2 10 7 5 9 9 11 12 14 20 15 16 19 18 17...

Page 17: ...nifold 1 6 901137 01 901137 02 Burner Pan 1 7 901242 01 901242 01 Damper Clamp Std Assy 1 8 101628 01 101628 01 Gas Line 10 Flex 1 9 901431 01 901431 01 Grate Steps 2 10 901246 01 901246 02 Log Grate...

Page 18: ...Y VALVE PILOT KIT GA9150A Not Shown For all models Required for remote control operation Contains components for propane LP conversion INDIVIDUAL ROUND LOG GA9450A Not Shown For decorative purposes on...

Page 19: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 20: ...his warranty The log set MUST be installed by a quali ed installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in ori...

Reviews: