- 81 -
Phenomenon
Assumed cause
Action
Engine will
not start u
p
Cell motor
will not run
or revolution
speed is low
Discharged battery
Charge or
replace
Detached or loosened or corroded
battery terminal
Repair
Fuse blow
Replace
Improper starter switch
Replace
Improper starter
Replace
Broken lead wire
Repair
Cell motor run
s
Fuel shortage
Supply
Blinded fuel filter
Replace cartridge
Air in fuel system
Remove
Speed will not rise
Air in fuel system
Remove
Blinded fuel filter
Replace cartridge
Compression failure
Repair engine
Blinded air cleaner
Replace element
Engine stop by oil failure
Oil shortage
Supply
Oil pressure switch failure
Replace
Blinded oil filter
Replace cartridge
Over heat
(
water temperature
)
Cooling water shortage
Supply
Fan belt looseness
Adjust
Blinded core of radiator
Clean
Engine thermostat failure
Repair
Voltmeter will not operate
Voltmeter failure
Replace
AVR failure
Contact
distributor or
our office
Burned ZNR
Quenched residual magnetism
Burned rotary rectifier
Disconnected rotor wiring
Burned generator wiring
Rated voltage will not be
reached
Voltmeter failure
Replace
AVR failure
Contact
distributor or
our office
VR failure
Burned rotary rectifier
Burned ZNR
Burned generator wiring
Low speed
Increase
Summary of Contents for DCA-150LSKE
Page 2: ...Japan...
Page 18: ...14 16 environmental base fluid level warning lamp...
Page 55: ...51 When the single parallel change over switch is parallel side device acts...
Page 93: ...89 12 2 Outline drawing...
Page 94: ...90 12 3 Generator connection diagram...
Page 95: ...91 12 4 Engine wiring diagram...
Page 96: ...92 12 5 Controller wiring diagram...
Page 101: ...97...