- 70 -
(5)
Check
on
battery
specific
gravity.
If
battery
is
likely
to
be
discharged
due
to
failure
in
startup
of
the
engine,
measure
the
specific
gravity
of
battery
acid.
The
relation
between
battery
charge
condition
(charging
rate)
and
specific
gravity
is
as
shown
below.
Liquid
temp.
Charging (
℃
)
rate(%)
20
0
-10
100
1.28
1.29
1.30
90
1.26
1.27
1.28
80
1.24
1.25
1.26
75
1.23
1.24
1.25
Each value has a deviation of
±
0.01.
When the charging rate is below 75%, the battery needs to be recharged.
「
8-1. Caution on battery charge
」
(6)
Emission carbon deposition check
Deposition of carbon (soot, unburned fuel) in the exhaust pipe line and muffler could cause not only
system derates but also could lead to fires. To destroy soot and unburned fuel, run the unit at rated
power until the exhaust gas become mostly colorless every 250 hours operation time. More carbon
will be generated when the unit operates at less then 30% of rated power. In this case, perform the
above procedures more frequently.
NOTE:
・
Applying a large load suddenly to the unit when the carbon deposition is generated in the exhaust
system could produce sparks and will lead to abnormal combustion. Therefore, apply load gradually
and observe the exhaust gas color during the process.
・
Sparks may come out of the exhaust gas outlet during load operation. Make sure the unit’s
surrounding is free from any flammable material.
Summary of Contents for DCA-150LSKE
Page 2: ...Japan...
Page 18: ...14 16 environmental base fluid level warning lamp...
Page 55: ...51 When the single parallel change over switch is parallel side device acts...
Page 93: ...89 12 2 Outline drawing...
Page 94: ...90 12 3 Generator connection diagram...
Page 95: ...91 12 4 Engine wiring diagram...
Page 96: ...92 12 5 Controller wiring diagram...
Page 101: ...97...