Checking/every
1000
hours
Checking/every
100, 250
and
500
hours
is
also
required.
(1)
Replacement
of
fuel
filter
cartridge.
①
Remove the cartridge type element (cartridge) using
filter wrench.
②
Clean the filter base. Coat the packing of new
cartridge with engine oil thin. Then, mount the
cartridge.
- When mounting, tighten the cartridge about from
1/2
to
3/4
turn
by
hand
after
the
packing
is
fitted
to
the
seal
of
the
filter
base.
③
After the cartridge is replaced, discharge air
in the fuel piping.
- For details, refer to the instruction manual
for the engine. A nameplate showing the
method of discharging air is also attached
to the machine.
Parts number of fuel filter cartridge :
Model name
Parts number manufacture Parts number of manufact
ure
DCA-150LSK
E
Y06020 42585
KOMATSU
600-319-3750
(2)
Internal cleaning of an environmental base
<
Division Procedure
>
①
Drain the water or contents collected in an environmental base.
②
Bolt that unites environmental base with upper base is detached with
the hook of the crane hung on the hanging metal fittings of this machine.
③
This machine is slowly lifted up, and it separates from an environmental base.
④
Check and clean the internal environmental base.
Summary of Contents for DCA-150LSKE
Page 2: ...Japan...
Page 18: ...14 16 environmental base fluid level warning lamp...
Page 55: ...51 When the single parallel change over switch is parallel side device acts...
Page 93: ...89 12 2 Outline drawing...
Page 94: ...90 12 3 Generator connection diagram...
Page 95: ...91 12 4 Engine wiring diagram...
Page 96: ...92 12 5 Controller wiring diagram...
Page 101: ...97...