8.3. Multiple XML/JSON access
With the
Multiple Access
option selected the password should be passed as a
non-encrypted parameter with each request:
http://192.168.1.100/current_state.xml?pw=admin
http://192.168.1.100/current_state.json?pw=admin
Multiple Access
is not allowed when
Encrypt Password
option is
enabled.
9. HTTP client
9.1. Data Logging mode
Data Logging mode (push notifications mode) is designed in order to help solving
cases like remote monitoring and Internet/Ethernet logging. The
SmartDEN IP-32IN
acts like a client and it sends (pushes) HTTP POST messages in XML format to the
HTTP server periodically (Fig. 55).
Figure 55.
Data logging mode
Data Logging
mode is adjusted from the "Remote Services Settings" web
page -> "Data Logging" section.
Please note the module does not support internal memory data storage for
logging, but it can send only messages to remote server-logger!
9.1.1. HTTP POST header
Bellow is shown the header of example POST message sent by
SmartDEN IP-