
SmartDEN
IP-32IN
User Manual
17 Jan 2018
-38-
count pulses with frequency about 1Hz or this is 500ms ON and
500ms OFF;
In case the controller is working with the EEPROM in that moment it
is not possible to count pulses due to the blocking time which may
be several seconds. This state is not suitable for counting pulses
but only for adjustments!
Filter (ms)
- the input may be adjusted to work with a digital filter. It is valid for
the input visualization, counting, SNMP traps and controlling the outputs as
well. This parameter sets the time (in milliseconds) for this filter and it can be
from 0 up to 200 ms;
SNMP Trap
- determines if the Digital Input will send traps or not;
SNMP Trap Value
-
this parameter determines how the traps will be sent and
how counter will work:
o
0 (Off)
- If the parameter
Trap Sending
is set with value "Level Triggered"
then the trap message is sent when the Digital Input is in low level (0)
every 5 seconds. If the parameter
Trap Sending
is set with value "Edge
Triggered" then the trap message is sent when the Digital Input's is falling
edge (1->0); In this mode the counter will be increased when the Digital
Input value transits from 1 to 0.
Figure 34.
Traps and counter when SNMP Trap Value is "0 (off)"
o
1 (On)
- If the parameter
Trap Sending
is set with value "Level Triggered"
then the trap message is sent when the Digital Input is in high level (1)
Summary of Contents for SmartDEN IP-32IN
Page 25: ...SmartDEN IP 32IN User Manual 17 Jan 2018 25 Remote Relay Mode Normal...
Page 49: ...SmartDEN IP 32IN User Manual 17 Jan 2018 49 7 14 Reboot Figure 51 Reboot...
Page 52: ...SmartDEN IP 32IN User Manual 17 Jan 2018 52 Figure 53 XML file with current measurements...
Page 54: ...SmartDEN IP 32IN User Manual 17 Jan 2018 54 Figure 54 JSON file with current measurements...
Page 66: ...SmartDEN IP 32IN User Manual 17 Jan 2018 66 12 Mechanical drawing Figure 59 Device size...