SmartDEN
IP-32IN
User Manual
17 Jan 2018
-32-
7.5. HTTP/XML/JSON
Figure 29.
HTTP/XML/JSON access
These settings let you configure the HTTP and XML/JSON access parameters of
SmartDEN IP-32IN:
HTTP Port
-
port that the Web server listens for HTTP requests (default port is
80). You have to reboot the device for a new port setting to apply;
Access IP Address/Access Mask
-
these fields can be used to restrict the
HTTP/XML/JSON access by specifying the IP address and subnet mask of the
HTTP client;
Access MAC Address
-
this field can be used to restrict the
HTTP/XML/JSON access by specifying the MAC address of the HTTP client;
Session Timeout, min
-
Specifies the timeout period for HTTP and
XML/JSON sessions in minutes;
Enable Access
-
this option enables or disables XML/JSON access to the
SmartDEN IP-32IN
;
Encrypt Password
-
when XML/JSON access is enabled, this option adds
additional security level by encrypting the login password;
Multiple Access
-
this option enables simultaneous XML/JSON access from
several HTTP clients;
Save button
-
once you have changed the settings as required, click this
button.
Summary of Contents for SmartDEN IP-32IN
Page 25: ...SmartDEN IP 32IN User Manual 17 Jan 2018 25 Remote Relay Mode Normal...
Page 49: ...SmartDEN IP 32IN User Manual 17 Jan 2018 49 7 14 Reboot Figure 51 Reboot...
Page 52: ...SmartDEN IP 32IN User Manual 17 Jan 2018 52 Figure 53 XML file with current measurements...
Page 54: ...SmartDEN IP 32IN User Manual 17 Jan 2018 54 Figure 54 JSON file with current measurements...
Page 66: ...SmartDEN IP 32IN User Manual 17 Jan 2018 66 12 Mechanical drawing Figure 59 Device size...