DAEnetIP3
User Manual
-
37
-
9.5.
High Threshold (HT)
This is the second threshold (limit) that is used for events generating. The value is
between 1 and 1023.
9.6.
Low Hysteresis (LH)
This value is the hysteresis for the Low Threshold. The value is between 1 and
512.
9.7.
High Hysteresis (HH)
This value is the hysteresis for the High Threshold. The value is between 1 and
512.
9.8.
Rules
(HT-HH)>(LT+LH)
(HT+HH)<1023
(LT-LH)>0
9.9.
Minimum value
This value is equal of ADC value = 0 divisions
9.10.
Maximum value
This value is equal of ADC value = 1024 divisions
9.11.
Label
This is the label in which is measured the analog input. It may be "V", "C", "RH"...
9.12.
Analog Input Mode
Generally there are 5 modes for the analog inputs:
9.12.1.
Simple reading
This mode is simple reading of the analog input value. There are no reactions
(events) based on this input. It is used only to retrieve the values from the analog
inputs (monitoring).