DAEnetIP3
User Manual
-
21
-
When DI is in “Set output during rising edge” mode, the DO is set in high
level during rising edge of the DI level. DO is set in low level during falling
edge of the DI level.
When DI is in “Set output during falling edge” mode, the DO is set in low
level during rising edge of the DI level. DO is set in high level during
falling edge of the DI level.
Figure 14.
On/Off setting and digital input
7.5.3.
On/Off setting and analog input
On figure 15 is shown the dependence between digital output (On/Off setting) and
analog input (the four modes). The user can not control manually the outputs in this
mode.
In “Low” mode the output level is set high when the rising analog input
level crosses the LT+LH/2 limit and set low when the falling analog input
level crosses the LT-LH/2 limit.
In “High” mode the output level is set low when the rising analog input
level crosses the HT+HH/2 limit and set high when falling analog input
level crosses the HT-HH/2 limit.
I
n “Acc” mode the output level is set high when the rising analog input
level crosses the HT+HH/2 and set low when the rising analog input level
crosses the LT-LH/2.
In “Low/High” mode the output level is set high when the rising (falling)
analog input level crosses the LT+LH/2 (HT-HH/2). The output level is set
low when the rising (falling) analog input level crosses the HT+HH/2 (LT-
LH/2).