83
Operation and Installation Manual for SOL10.0-1TR3-E4 and SOL11.0-1TR3-E4
15. Technical data
EN
15. Technical data
Input (DC)
SOLIVIA 10 TR
SOLIVIA 11 TR
Maximum recommended PV power
12,100 W
P
13,300 W
P
Rated power
10,600 W
11,600 W
Maximum input voltage
1,000 V
1,000 V
Input voltage range for grid feeding
1)
375 ... 1,000 V
375 ... 1,000 V
MPP working range
375 ... 850 V
375 ... 850 V
Rated current
17.7 A at 600 V
19.5 A at 600 V
Maximum operating current
26.4 A
29 A
Maximum allowed current load at the DC input
29 A
29 A
Overvoltage category
III
III
Output (AC)
SOLIVIA 10 TR
SOLIVIA 11 TR
Rated apparent power
1)
10,000 VA
11,000 VA
Voltage range (3 phases, 5-conductor)
2)
3 x 400 V + N + PE (+18/-20 %) 3 x 400 V + N + PE (+18/-20 %)
Rated current
14.5 A (per phase)
16 A (per phase)
Maximum current
20 A
20 A
Rated frequency
50 Hz
50 Hz
Frequency range
2)
50 Hz ± 5 Hz
50 Hz ± 5 Hz
Power factor (cos φ)
3)
> 0.99 at rated apparent power > 0.99 at rated apparent power
Power factor configuration area
0.8 cap ... 0.8 ind
0.8 cap ... 0.8 ind
Total harmonic distortion (THD)
< 5% at rated apparent power
< 5% at rated apparent power
Nighttime consumption
< 1.3 W
< 1.3 W
Typical leakage current
<3.5 mA
<3.5 mA
Overvoltage category
III
III
1)
At cos φ = 1 (VA = W)
2)
AC voltage and frequency ranges are programmed according to the respectively applicable national regulations
Standards/Guidelines
SOLIVIA 10 TR
SOLIVIA 11 TR
Degree of protection
4)
IP65/IP54
IP65/IP54
Safety class
I
I
Configurable switch-off parameters
Yes
Yes
Isolation monitoring
Yes
Yes
Overload behavior
Current limiting, power limiting
Current limiting, power limiting
ENS/grid connection guidelines
DIN VDE 0126-1-1;
VDE-AR-N 4105 (low voltage
directive); Synergrid C10/11
(July 2012)
DIN VDE 0126-1-1; UTE C15-
712-1; France/islands(60 Hz);
RD 661/2007; RD 1699/2011;
RD 1663/2000; Synergrid
C10/11 (July 2012); EN 50438;
G59/1-2; VDE-AR-N 4105;
BDEW
EMV
EN61000-6-2, EN61000-6-3,
EN61000-3-11, EN61000-3-12
EN61000-6-2, EN61000-6-3,
EN61000-3-11, EN61000-3-12
Safety
IEC62103, IEC62109-1/-2
IEC62103, IEC62109-1/-2
4)
IP65 for electronics/IP54 for cooling area