27
Operation and Installation Manual for SOL10.0-1TR3-E4 and SOL11.0-1TR3-E4
7. Installation
EN
DC Connection of
Power Inverter
Connection T
ype
for Cable
W
ire Cross-Section
Diameter Range for
Cable Sheath
Multi-Contact
Order
no.
mm
2
AWG mm
DC+ Socket
1.5 / 2.5 14
3-6
32.0010P0001-UR
5.5-9
32.0012P0001-UR
4 / 6
10
3–6
32.0014P0001-UR
5.5-9
32.0016P0001-UR
DC-
Plug
1.5 / 2.5 14
3-6
32.0011P0001-UR
5.5-9
32.0013P0001-UR
4 / 6
10
3-6
32.0015P0001-UR
5.5-9
32.0017P0001-UR
Multi-Contact UTE kit (for France)
The Multi-Contact UTE Kit is designed to conform to the latest
French standard UTE C 15-712-1. It contains eight couplings,
an installation and removal key and a signal sticker. This UTE kit
allows you to meet the DC protection and signal requirements
specifi ed in UTE C 15-712-1.
Multi-Contact UTE Kit
Delta Part num-
ber
Multi-Contact UTE kit for SOLIVIA EU G4 TR EOE90000341
7.4.3 Establishing Connection
1. Check the polarity of the DC voltage at the DC connections
before connecting the PV system.
2. Install the connection plug/socket on the DC cable. Follow the
connection plug manual when doing this.
3. Insert the DC cable into the DC connections for the solar
power inverter.
4. Check the installation.
þ
The PV module is now connected.
7.4.4 Grounding DC Side
The solar power inverter can be grounded at either the DC+ side
or the DC- side. The ground connection must be installed near the
solar power inverter. We recommend using the grounding kit from
Delta.
The DC side of the solar power inverter has an insulation and
grounding monitor. Monitoring can be confi gured in the
230
Grounding
menu, see
“10.13 Insulation and grounding monitor-
ing”, p. 63
.
► Install the ground kit according to the manual delivered with
the kit.