8. Commissioning
Operation and Installation Manual for SOLIVIA 10.0 / 11.0 EU G4 TR
46
➔
Baudrate: 19200
ID: 1
-------------------
RS485
15. To change the value, press the button and then set
the value using the
buttons. Press the button to
apply the value.
nOTE
: If multiple solar power invert-
ers are to be connected via RS485,
select a different ID for each inverter.
The ID is also used when saving and
loading settings in order to identify the
solar power inverter.
Available IDs:
1 ... 254
Available baudrates:
2400 | 4800 | 9600 | 19200 | 38400
Confi guration option RS485 termina-
tion resistor:
On | Off
➔
Termination: On
Baudrate: 19200
ID: 1
continue
-------------------
RS485
16. Press the
buttons to select
continue
and then
press the button.
→ The completion screen will be displayed.
to reselect
ESC:
to confirm
ENTER:
17. Press the button to complete commissioning.
or
Press the
ESC
button to change settings.
þ
Commissioning is now fi nished.
nOTE
► If the solar power inverter is confi gured to the
DE LVD,
DK LVD
or
DE MVD
grids, you can also confi gure active and
reactive power control, see
“10.9 Active power control”, p. 56
and
“10.10 Reactive Power Control”, p. 58
.
► The solar power inverter offers some optional functions available for all grids, see
“10 Settings”, p. 52.
► On completion of commissioning, save the settings (see
“11.5 Saving settings”, p. 68
) and the swap data (see
“11.7 Saving swap data”, p. 70
) on a USB stick so that you can use this information later.