5.4 DC Connection
The maximum open circuit voltage of the PV Array must not exceed 600Vdc.
CAUTION !
WARNING !
•
When undertaking DC wiring, please ensure the correct polarities are connected.
•
When undertaking DC wiring, please ensure that the DC isolator switch
on the
PV array is OFF.
•
When undertaking BAT wiring, please ensure that the BX6.3_DD system is shutdown.
The isolator installed between the PV Array and inverter must meet the rating
of voltage higher than this device’s maximum input voltage.
NOTE
Installation of the AC Cable Gland
1
.
Loosen the front cover
①
counterclockwise.
2
.
Remove the rubber washer
②
from the fastening ring
③
.
3
.
Connect the cable with the terminal.
4. Install the rubber washer
②
to the fastening ring
③
.
5. Surely tighten the front cover
①
.
①
②
③
* Cable range: 14 - 18 mm
5.4.1 PV connector
The inverter operate using two separate MPP trackers that can handle both
symmetrical and asymmetrical loads to allow for optimum adjustment.
This allows for the requirements of complex PV system designs to be fulfilled.
MPP range with Max. power
Symmetrical load
Asymmetrical load
Max. ratio for asymmetrical load
H8E/H10E
280~480V
280~480V
81/19%;19/81%
M25
Wiring
19