Delta Elektronika SM120-25D Product Manual Download Page 9

DESCRIPTIONS

SM3000

Page 3 - 6

DELTA ELEKTRONIKA B.V.

rev. February 2018

26)

SERIES  OP ER A TION

Se ries op er a tion is al lowed up to 600 V to tal volt age. The power sup plies
can be con nected in se ries with out spe cial pre cau tions.
For eas ier con trol, Mas ter / Slave op er a tion is rec om mended (see fig.  3 -
20). By us ing the Mas ter / Slave Se ries fea ture a 

dual track ing

 power sup -

ply can be made with one unit as mas ter and one as slave.
For se ries op er a tion in com bi na tion with Power Sink op tion, all units must
have a Power Sink built in side oth er wise no power can be ab sorbed. 

27)

PAR AL LEL  OP ER A TION

Par al leling of the units has no lim i ta tions. The power sup plies can be con -
nected in par al lel with out spe cial pre cau tions. For eas ier con trol, Mas ter /
Slave op er a tion is rec om mended  (see fig. 3 - 20 and fig. 3 - 21).
Nor mal  par al lel  op er a tion  of 

Fast  Pro gram ming

 units can give prob lems,

each com bi na tion has to be tested first, in com bi na tion with the load ! 
For  par al lel  op er a tion  in  com bi na tion  with 

Power Sink

 op tion, only one unit

can have a Power Sink. Re fer to Power Sink man ual for de tails and re stric -
tions.

28)

MASTER / SLAVE OP ER A TION

The Mas ter / Slave fea ture makes it pos si ble to use the power sup plies as
build ing blocks to form one large unit (see fig. 3 - 21). 
The re sult ing com bi na tion of units be haves like one power sup ply and can
be pro grammed on the mas ter. Fig ure 3 - 23 shows a com puter con trolled 
M/S  par al lel  com bi na tion.
Mixed par al lel - se ries op er a tion is also pos si ble (see fig. 3 - 22), to a max i -
mum of 600 V. Here the 

MAS TER / SLAVE

  

SE RIES  ADAPTER

 

(

δ

-prod uct)

must be used. For par al lel op er a tion con nec tions can eas ily be made on
the  an a log  pro gram ming  con nec tor.
In se ries mode the mas ter con trols one slave, which in turn con trols the
sec ond slave and so on. In par al lel mode the mas ter con trols all the slaves. 
The re sult is true 

cur rent or volt age shar ing

 in the par al lel or se ries mode

re spec tively.

Note: Mas ter / Slave par al lel op er a tion is not rec om mended for more
than 3 units or in com bi na tion with Fast Pro gram ming op tion. 
Con sult fac tory for a so lu tion.

29)

RE MOTE  SENSING

The volt age at the load can be kept con stant by re mote sens ing. This fea -
ture is not rec om mended for nor mal use but only when the load volt age is
not al lowed to vary a few mil li volts. Al ways use a 

shielded ca ble

 for sens -

ing.
In or der to com pen sate for the volt age drop across the load leads, the unit
will have to sup ply a higher volt age: U

out 

= (volt age drop across each lead)

+ (volt age across the load) (see fig. 3 - 24). The 

OVP

 reads the volt age di -

rectly at the out put and the set ting must be in creased by the to tal volt age
drop across the load leads.
The volt me ter is con nected to the sense leads and there fore reads the volt -
age across the load and 

not

 the volt age on the out put ter mi nals.

The sense leads are pro tected for 

ac ci den tal  in ter rup tion

, in which case

the out put volt age will go to a max. of 115% of the set value.

Warn ing:

 Do not in ter rupt the mi nus lead while the S– lead is still con -

nected to the load, dur ing op er a tion.
For sens ing on a 

pul sat ing  load

, see pre vi ous paragraph 17).

30)

OVP

The Over Volt age Pro tec tor will pro tect your cir cuit from un wanted high
volt ages. 
A high out put volt age could be caused by ac ci den tal in ter rup tion of leads,
ac ci den tally  turn ing  up  the  volt age  potmeter or a de fect in the power sup -
ply. The OVP cir cuit uses a sep a rate volt age di vider con nected di rectly to
the  out put  ter mi nals.
The  OVP lim its the out put volt age to a value which can be set by the OVP
potmeter on the front panel. While do ing this, press the DIS PLAY OVP
SETTING but ton to read the limit value in the left dis play. The led on the
front panel will in di cate whether the OVP has reached the limit. The OVP
sta tus out put will give a logic 1 (+5 V).

Note: The Ther mal ShutDown and Re mote ShutDown will also cause the
OVP-led to burn and the OVP-status will be high.

fig. 3 - 20

Mas ter / Slave ser ies operation

fig. 3 - 21

Mas ter / Slave parallel operation

fig. 3 - 22

Mas ter / Slave mixed se ries-parallel

fig. 3 - 23

The Mas ter / Slave com bi na tion can also 

be pro grammed with the in ter faces

PSC-488 or the PSC-232

Summary of Contents for SM120-25D

Page 1: ...rlands www DeltaPowerSupplies com Tel 31 111 413656 SM3000 series PRODUCT MANUAL Contents 1 Datasheet 2 Safety Instructions 3 Descriptions 4 Operating Trouble Shooting Calibration 5 EC Declaration of...

Page 2: ...ution 3 When programming a high voltage unit directly via a PC or via a network connection either ground the negative power output or use a safety isolated interface For more information and schematic...

Page 3: ...d separately to recycle it responsibly to promote the sustainable reuse of material resources 11 Removal of safety covers Safety cover s are used to cover potentially hazardous voltages Observe the fo...

Page 4: ...2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 90 of t...

Page 5: ...programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that the analog inputs and outputs ar...

Page 6: ...gh 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Page 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Page 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Page 9: ...recommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fe...

Page 10: ...ure and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it wil...

Page 11: ...ITER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating swit...

Page 12: ...mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage sour...

Page 13: ...erminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set at t...

Page 14: ...ended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power connecti...

Page 15: ...ON For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units in ser...

Page 16: ...ly to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment An ag...

Page 17: ...nt is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programming can...

Page 18: ...ry to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a short SM...

Page 19: ...h exactly 5 00 V Set output voltage to a low value ensuring the power supply is in CC mode Measure the output current with an accurate shunt Cali brate the current with R686 exactly on the rated max c...

Page 20: ...al EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage fluctuation and flicker EN 61000 6 1 Generic Immunity residential light industrial EN 61000 6 2 Generic Immunity industrial environment...

Reviews: