Delta Elektronika SM120-25D Product Manual Download Page 12

SM3000

OPERATING - TROUBLE SHOOTING - CALIBRATING

rev. February 2018

DELTA ELEKTRONIKA B.V.

Page 4 - 1

4   OPERATING MANUAL

1)

OP ER ATING THE UNIT FOR THE FIRST TIME 

Check that there is no con den sa tion on the unit. If there is, al low
some time to dry.

Set the pro gram switches on the rear panel on MAN UAL.

Check that there is a link be tween + and S+ and be tween – and
S– on the SENSE BLOCK (on rear panel)

Set OVP po ten ti om e ter (on front panel) to max i mum (fully clock -
wise), Use a screw driver to set the OVP volt age.

With 

high out put cur rent 

make sure to use low re sis tive con -

nec tions be tween the power sup ply and the load:

- Mount the ca ble lugs di rectly on the tinned out put strips 
  fol lowed by a washer and a nut (see fig. 4 - 1). Al ways in 
  this or der!
- Never place ex tra wash ers be tween the lugs and the strips!
- Only use nuts and wash ers sup plied with the unit.

Switch on unit.

Turn both the CV and CC po ten ti om e ter a few turns clock wise. A
volt age should now be pres ent on the out put.

By press ing the DIS PLAY CV/CC SETTING but ton the me ters
will show the set ting of the CV and CC po ten ti om e ter.

By press ing the DIS PLAY OVP SETTING but ton the volt me ter
will show the set ting of the OVP  po ten ti om e ter.

When the power sup ply is used on a fixed out put volt age it is
highly rec om mended to set the Over Volt age Pro tec tor. As set
out in the fol low ing ta ble:

SM15-200D SM30-100D

SM45-70D

SM70-45D

SM120-25D SM300-10D

Vout + 2 V

Vout + 3 V

Vout + 5 V

Vout + 5 V

Vout + 10 V Vout + 25 V

Ex am ple: For a SM30-100D set at 24 V out put volt age it is rec om -
mended to set the OVP on 24 + 3 = 27 V.

Check that the cool ing of the unit is not ob structed.

2)

AN A LOG    PRO GRAMMING

Put the ap pro pri ate switch(es) in the po si tion PRO GRAM.

Con nect the pro gram ming volt age source(s) (0 - 5 V) to the AN A -
LOG PROG. CON NEC TOR on the rear panel (see fig. 4 - 2 and
fig. 4 - 3). Al ways use a 

shielded ca ble

 for pro gram ming.

If only the volt age is pro grammed, the max i mum cur rent can still
be set with the CC po ten ti om e ter and vice versa. If this is not de -
sir able the CC or CV can be set with an ex ter nal po ten ti om e ter, in 
or der to have a fixed set ting.

CAU TION

: The an a log in puts are not iso lated from the out put.

The Ø of the prog. in put (pin 1) is in ter nally con nected to the S–,
the S– is con nected to the neg a tive out put. To pro tect the in ter nal 
wir ing a 650 mA self-re set ting fuse is con nected in se ries (F600
on P432) (see fig. 3 - 10).

For  iso lated  an a log  pro gram ming  the 

ISO AMP CARD

 

(

δ

-prod -

uct)

 is rec om mended to avoid earth loops.

To avoid hum or noise, the pro gram ming ca ble may have to be 
twisted in some cases.

To pro gram the unit by cur rent in stead of volt age, sim ply use a
par al lel re sis tor as a cur rent to volt age con verter.

3)

IEEE488 / RS232  PRO GRAMMING

Set both prog. switches to the po si tion pro gram.

Both CV and CC can be pro grammed and read back. The CC and 
OVP sta tus can also be read by the com puter.

4)

MON I TORING  OUT PUTS

The 5 V level is com pat i ble with most in ter faces.

The mon i tor ing out puts can drive a me ter di rectly (see fig. 4 - 4).

fig.  4 - 1

Low  re sis tive  ca ble  con nec tion  by  mount ing  the 

ca bles di rectly on the tinned out put strips

fig. 4 - 2

Pro gram ming  by  volt age:

left volt age -, right cur rent pro gram ming

fig. 4 - 3

Pro gram ming  by  cur rent

left volt age -, right cur rent pro gram ming

fig. 4 - 4

Re mote  con trol

Summary of Contents for SM120-25D

Page 1: ...rlands www DeltaPowerSupplies com Tel 31 111 413656 SM3000 series PRODUCT MANUAL Contents 1 Datasheet 2 Safety Instructions 3 Descriptions 4 Operating Trouble Shooting Calibration 5 EC Declaration of...

Page 2: ...ution 3 When programming a high voltage unit directly via a PC or via a network connection either ground the negative power output or use a safety isolated interface For more information and schematic...

Page 3: ...d separately to recycle it responsibly to promote the sustainable reuse of material resources 11 Removal of safety covers Safety cover s are used to cover potentially hazardous voltages Observe the fo...

Page 4: ...2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 90 of t...

Page 5: ...programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that the analog inputs and outputs ar...

Page 6: ...gh 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Page 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Page 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Page 9: ...recommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fe...

Page 10: ...ure and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it wil...

Page 11: ...ITER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating swit...

Page 12: ...mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage sour...

Page 13: ...erminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set at t...

Page 14: ...ended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power connecti...

Page 15: ...ON For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units in ser...

Page 16: ...ly to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment An ag...

Page 17: ...nt is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programming can...

Page 18: ...ry to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a short SM...

Page 19: ...h exactly 5 00 V Set output voltage to a low value ensuring the power supply is in CC mode Measure the output current with an accurate shunt Cali brate the current with R686 exactly on the rated max c...

Page 20: ...al EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage fluctuation and flicker EN 61000 6 1 Generic Immunity residential light industrial EN 61000 6 2 Generic Immunity industrial environment...

Reviews: