Delta Elektronika SM120-25D Product Manual Download Page 20

rev. February 2018

DELTA ELEKTRONIKA B.V.

Page 5 - 1

SM3000

EC DECLARATION

We

Delta Elektronika
Vissersdijk 4
4301 ND  ZIERIKZEE
The  Neth er lands

De clare  un der  sole  re spon si bil ity  that  the  fol low ing  Power  Sup plies:

SM

 

15-200 D

SM

 

30-100 D

SM

 

45-70 D

SM

 

70-45 D

SM

 

120-25 D

SM

 

300-10 D

Meet  the  in tent  of  Di rec tives  2014/30/EC  for  Elec tro mag netic  Com pat i bil ity  and
Di rec tives  2014/35/EC  re gard ing  Elec tri cal  Safety.  (Low  Volt age  Di rec tive)
Com pli ance  was  dem on strated  to  the  fol low ing  spec i fi ca tion  as  listed  in  the  of fi cial  Jour nal
of  the  Eu ro pean  Com mu ni ties:

EN 61000-6-3 Ge neric Emis sions: 

(res i den tial,  light  in dus trial)

EN 55022 Ra di ated and con ducted, Class 

B

EN 61000-3-3 Volt age fluc tu a tion and flicker

EN 61000-6-1 Ge neric Im mu nity: 

(res i den tial,  light  in dus trial)

EN 61000-6-2 Ge neric Im mu nity: 

(in dus trial  en vi ron ment)

EN 61000-4-2 Elec tro static Dis charge
EN  61000-4-3  Ra di ated  elec tro mag netic  fields
EN 61000-4-4 Elec tri cal Fast Tran sients / Bursts
EN 61000-4-5 Surge on DC out put
EN 61000-4-5 Surge on line in put
EN 61000-4-6 RF com mon mode, con ducted
EN 61000-4-11 Volt age vari a tions and dips

EN 60950 Safety of IT equip ment

EN 61010 Safety of elec tri cal equip ment for mea sure ment, con trol and lab o ra tory use

EC  Dec la ra tion  of  Con for mity  -  SM3000-series

Man ag ing  di rec tor
Zierikzee,  Feb ru ary  2018

DC POWER SUPPLIES

DELTA

 

ELEKTRONIKA B.V.

Vissersdijk 4, 4301 ND
Zierikzee, the Netherlands

www.DeltaPowerSupplies.com
Tel.  +31 111 413656

Summary of Contents for SM120-25D

Page 1: ...rlands www DeltaPowerSupplies com Tel 31 111 413656 SM3000 series PRODUCT MANUAL Contents 1 Datasheet 2 Safety Instructions 3 Descriptions 4 Operating Trouble Shooting Calibration 5 EC Declaration of...

Page 2: ...ution 3 When programming a high voltage unit directly via a PC or via a network connection either ground the negative power output or use a safety isolated interface For more information and schematic...

Page 3: ...d separately to recycle it responsibly to promote the sustainable reuse of material resources 11 Removal of safety covers Safety cover s are used to cover potentially hazardous voltages Observe the fo...

Page 4: ...2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 90 of t...

Page 5: ...programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that the analog inputs and outputs ar...

Page 6: ...gh 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Page 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Page 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Page 9: ...recommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fe...

Page 10: ...ure and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it wil...

Page 11: ...ITER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating swit...

Page 12: ...mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage sour...

Page 13: ...erminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set at t...

Page 14: ...ended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power connecti...

Page 15: ...ON For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units in ser...

Page 16: ...ly to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment An ag...

Page 17: ...nt is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programming can...

Page 18: ...ry to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a short SM...

Page 19: ...h exactly 5 00 V Set output voltage to a low value ensuring the power supply is in CC mode Measure the output current with an accurate shunt Cali brate the current with R686 exactly on the rated max c...

Page 20: ...al EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage fluctuation and flicker EN 61000 6 1 Generic Immunity residential light industrial EN 61000 6 2 Generic Immunity industrial environment...