Delta Elektronika SM120-25D Product Manual Download Page 17

OPERATING - TROUBLE SHOOTING - CALIBRATING

SM3000

Page 4 - 6

DELTA ELEKTRONIKA B.V.

rev. February 2018

TROUBLE SHOOTING

1)

GEN ERAL

In case you need as sis tance for re pair ing a unit, please con tact
our en gi neers us ing the ad dress "

[email protected]

".

In case you want us to re pair the unit, please first fill out the
RMA-form be fore send ing the unit to us. Add ing a de tailed fault
de scrip tion will help us to re pair the unit as soon as pos si ble.
On our website 

www.DeltaPowerSupplies.com

 the RMA-form

can be found un der 'Sup port'.

2)

NO  OUT PUT  (nor mal  op er a tion)

Check in put fuses.

Check po si tion of prog. switches at the rear panel, they should be
on MAN UAL.

Check the con nec tions on the SENSE BLOCK (at rear panel),
there should be a link be tween + and S+ and be tween – and S–.

Set  OVP po ten ti om e ter (at front panel) at max i mum (fully clock
wise).

Switch on unit.

Turn both the CV and CC po ten ti om e ter a few turns clock-wise. A
volt age should be pres ent on the out put.

3)

PRO GRAMMING DOES NOT WORK OK

Check po si tion of prog. switches at rear panel.

The unit works OK in man ual con trol,

 but in pro gram ming

mode the out put volt age / cur rent has a large er ror.
Prob a bly the fuse in se ries with Ø (pin 1) of prog. connector trip -
ped, the fuse (F600 = 650 mA) is a self-resetting type (see
fig. 4 - 16).

To check the fuse (F600) mea sure the volt age be tween Ø and the
mi nus out put, dur ing the fault con di tion. The volt age should only
be a few mV, a high volt age means that an un wanted cur rent is
flow ing through pin 1 of the prog. con nec tor.
Please check why cur rent is flow ing through pin 1 (see also next
para graph  4) and fig. 4 - 17).

4)

PRO GRAMMING  OFF SETS

Un wanted off sets in the pro gram ming can  be caused by
earth loops.

Fig ure  4 - 17 shows a typ i cal earthing prob lem. In case the load
has a con nec tion to earth and the pro gram ming source as well,
prob lems could oc cur.  Im proper choice of the earthing point of the 
load can give a volt age drop of 

V1.  Con necting the mi nus or zero 

to a sep a rate earth con nec tion can give a volt age drop of 

V2. Be -

cause the in ter nal wires of the pro gram ming in put are thin, the
volt age drops  

V1 and  

V2 will be across the in ter nal wir ing as

well. Re sulting in a er ror volt age in se ries with the pro gram ming
volt age.

The best 

so lu tion

 for this is us ing a float ing pro gram ming source

with the help of the 

ISO AMP CARD

 

(

δ

-prod uct)

 or a float ing load.

5)

STATUS OUTPUTS FAIL

Check fuse F601 in se ries with Ø (pin 8) (see fig. 4 - 16). To check
the fuse (F601) mea sure the re sis tance be tween Ø and the mi nus
out put, an open cir cuit means a blown fuse. F601 = 650 mA.

6)

MASTER / SLAVE PAR AL LEL PROB LEMS

Ac ci den tal  in ter rup tion  of  a  mi nus  lead  of  a  unit  dur ing  op er a tion
will cause fuse F600 to blow (see fig. 4 - 16). To check the fuse
(F600) mea sure the re sis tance be tween Ø (pin 1 of prog. conn.)
and the mi nus out put, the fuse is a self re set ting type.
F600 = 650 mA

Check link be tween pin 9 and 11 on the prog. con nec tor of the

slaves

Cur rent shar ing is not ok. Prob a bly the links be tween S– and – of
the

 slaves

 are not re moved.

fig. 4 - 16

Lo ca tion of pro gram ming fuses on P432

P432 is sit u ated on the rear panel

fig. 4 - 17

Un wanted  pro gram ming  off sets

Summary of Contents for SM120-25D

Page 1: ...rlands www DeltaPowerSupplies com Tel 31 111 413656 SM3000 series PRODUCT MANUAL Contents 1 Datasheet 2 Safety Instructions 3 Descriptions 4 Operating Trouble Shooting Calibration 5 EC Declaration of...

Page 2: ...ution 3 When programming a high voltage unit directly via a PC or via a network connection either ground the negative power output or use a safety isolated interface For more information and schematic...

Page 3: ...d separately to recycle it responsibly to promote the sustainable reuse of material resources 11 Removal of safety covers Safety cover s are used to cover potentially hazardous voltages Observe the fo...

Page 4: ...2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 90 of t...

Page 5: ...programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that the analog inputs and outputs ar...

Page 6: ...gh 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Page 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Page 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Page 9: ...recommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fe...

Page 10: ...ure and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it wil...

Page 11: ...ITER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating swit...

Page 12: ...mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage sour...

Page 13: ...erminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set at t...

Page 14: ...ended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power connecti...

Page 15: ...ON For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units in ser...

Page 16: ...ly to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment An ag...

Page 17: ...nt is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programming can...

Page 18: ...ry to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a short SM...

Page 19: ...h exactly 5 00 V Set output voltage to a low value ensuring the power supply is in CC mode Measure the output current with an accurate shunt Cali brate the current with R686 exactly on the rated max c...

Page 20: ...al EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage fluctuation and flicker EN 61000 6 1 Generic Immunity residential light industrial EN 61000 6 2 Generic Immunity industrial environment...

Reviews: