Delta Elektronika SM120-25D Product Manual Download Page 7

DESCRIPTIONS

SM3000

Page 3 - 4

DELTA ELEKTRONIKA B.V.

rev. February 2018

14)

PRO GRAMMING  BAND WIDTH

For small sig nals the band width is 50 Hz, but for large sig nals
there is a lim i ta tion in the max i mum am pli tude of the out put wave -
form. The out put ca pac i tors limit the max. slew rate. Fig ure 3 - 13
shows the max i mum peak to peak out put volt age swing as a
func tion of fre quency, with the load as a pa ram e ter. The higher
the load re sis tance the lower the max. am pli tude. The mea sure -
ments were car ried out us ing a sine wave. The DC level of the
out put is 50 % of the max. out put volt age.

15)

RE COVERY  TIME

Fig ure  3 - 14 shows the re cov ery time for the SM30-100D at
25 °C,  set at 30 V out put volt age, with a 50 – 100% load step.

16)

NOISE SUP PRES SION (in put / out put)

The in put / out put noise sup pres sion is mea sured with a pulse
gen er a tor (a) in se ries with the line in put or (b) be tween in put and
case (earth). The gen er a tor should pro duce a high en ergy pulse
of about 300 V. If there is an elec tri cal con nec tion be tween the
out put and the in put through the os cil lo scope, you will get a false
read ing. The sup pres sion for the SM120-25D is lower, but the
rel a tive  dis tur bance  on  the  out put  is  com pa ra ble  to  the
SM30-100D.

17)

PUL SATING  LOAD

To avoid over heat ing the out put ca pac i tors, the AC com po nent
of the load cur rent should be lim ited (see fig. 3 - 15).
One method of de creas ing the AC cur rent through the out put ca -
pac i tor  is  by  us ing  a  large  ex ter nal  elec tro lytic  ca pac i tor  in  par al -
lel with the load. Care must be taken so that the ca pac i tor in
com bi na tion with the lead in duc tance will not form a se ries res o -
nant cir cuit!
When us ing 

re mote  sens ing

 on a pul sat ing load (for in stance a

DC-mo tor), use a ca pac i tor in se ries with a re sis tor over the load
(see fig. 3 - 16). Like this the AC-com po nent caused by the pul -
sat ing of the load is fil tered.
With pul sat ing loads the 

I-monitor out put 

should not be used.

fig. 3 - 13

Max. peak to peak out put volt age swing vs fre quency

fig. 3 - 14

Re cov ery  time  SM30-100D

50 - 100 % load step, Vo=30 V

fig. 3 - 15

Pul sating load current

Summary of Contents for SM120-25D

Page 1: ...rlands www DeltaPowerSupplies com Tel 31 111 413656 SM3000 series PRODUCT MANUAL Contents 1 Datasheet 2 Safety Instructions 3 Descriptions 4 Operating Trouble Shooting Calibration 5 EC Declaration of...

Page 2: ...ution 3 When programming a high voltage unit directly via a PC or via a network connection either ground the negative power output or use a safety isolated interface For more information and schematic...

Page 3: ...d separately to recycle it responsibly to promote the sustainable reuse of material resources 11 Removal of safety covers Safety cover s are used to cover potentially hazardous voltages Observe the fo...

Page 4: ...2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 90 of t...

Page 5: ...programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that the analog inputs and outputs ar...

Page 6: ...gh 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Page 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Page 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Page 9: ...recommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fe...

Page 10: ...ure and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it wil...

Page 11: ...ITER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating swit...

Page 12: ...mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage sour...

Page 13: ...erminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set at t...

Page 14: ...ended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power connecti...

Page 15: ...ON For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units in ser...

Page 16: ...ly to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment An ag...

Page 17: ...nt is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programming can...

Page 18: ...ry to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a short SM...

Page 19: ...h exactly 5 00 V Set output voltage to a low value ensuring the power supply is in CC mode Measure the output current with an accurate shunt Cali brate the current with R686 exactly on the rated max c...

Page 20: ...al EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage fluctuation and flicker EN 61000 6 1 Generic Immunity residential light industrial EN 61000 6 2 Generic Immunity industrial environment...

Reviews: