Delta Elektronika SM120-25D Product Manual Download Page 5

DESCRIPTIONS

SM3000

Page 3 - 2

DELTA ELEKTRONIKA B.V.

rev. February 2018

The in put cir cuit has a large se ries choke to im prove the wave form. The re -
sult is: a lower rms in put cur rent, less mains dis tor tion and no large peak cur -
rents.
The units also have an in rush cur rent lim iter and a soft start cir cuit, for
smooth switch on.

°

FUSES  16 A Slow blow.

4)

STANDBY IN PUT POWER

The unit con sumes very lit tle power when in standby. This makes it pos si ble
to leave the in put power on and use the Re mote Shut Down in put (pin 5 on
prog. connector rear panel) to dis able the out put.

5)

EFFICIENCY

The ef fi ciency is very high and con stant over a wide out put cur rent range
(see fig. 3 -  4). High ef fi ciency also means low power loss and low heat gen -
er a tion.

6)

REG U LA TION

The load reg u la tion should be mea sured di rectly on the out put ter mi nals. 
A few cm of ca ble can have a volt age drop of sev eral mV (at high cur rent!).

7)

RIP PLE & NOISE

The out put rip ple is very low with al most no spikes.
The rip ple volt age has to be mea sured di rectly on the out put ter mi nals us ing
a probe with very short con nec tions (to avoid pick up of mag netic fields) (see
fig. 3 - 5 and fig. 3 - 6).
At  low  tem per a tures  like  -20

°

C the rip ple in creases. By us ing high qual ity

elec tro lytic  ca pac i tors  the  in crease  is  rel a tively  low.

8)

PRO GRAMMING  IN PUTS

The out put volt age and cur rent can be pro grammed by an ex ter nal an a log
volt 

age. This pro 

gram 

ming is very ac 

cu 

rate and lin 

ear, (non-lin ear ity

<0.15%). The lev els are all stan dard ized on 5V. Al ways use a 

shielded ca -

ble

 for pro gram ming.

The in puts have a pro tec tion cir cuit formed by a se ries re sis tor and a par al lel
zener (see fig. 3 - 7). The ca pac i tor lim its the speed to a safe value. Note that
the an a log in puts (and out puts) are 

not float ing, but the com mon is con -

nected to the neg a tive out put ter mi nal. 

Wrong  con nec tion  of  Ø can cause 

earth loops which can trip the fuse. Af ter re mov ing the fault, the fuse will re -
set (PTC-fuse). To pre vent earth loops, use iso lated pro gram ming with the

ISO AMP CARD in ter nal in ter face op tion P145(

δ

-prod uct)

.

The pro gram ming mode (pro gram and man ual) can be se lected by means of 
the prog. switches which are sit u ated be low the pro gram ming con nec tor
(see fig. 3- 9).

9)

IEEE488 / RS232  PRO GRAMMING

For  pro gram ming  use  the  ex ter nal  in ter face

  PSC-488 mod ule 

or  in ter nal  in -

ter face   

PSC-232 

(both 

δ

-prod ucts)

Volt age and cur rent can eas ily be pro grammed and read back. Also the CC
and OVP sta tus can be read by the com puter. Al ways use a 

shielded ca ble

for  pro gram ming.

10)

MON I TORING  OUT PUTS

The mon i tor out puts give a volt age 0 - 5 V pro por tional to the out put cur rent
or volt age. The out put cur rent can eas ily be mea sured with out an ex ter nal
shunt us ing the I-mon i tor (see fig. 3 - 8). The mon i tor out puts are buf fered by
op-amp’s and pro tected by se ries re sis tors and par al lel zeners (see fig. 3 -
10). The ta ble  3 - 1 shows the im ped ance lev els of the mon i tor ing out puts.
For us ing Imon on a pul sat ing load, see para graph 17) of this chapter.

fig. 3 - 4

Ef fi ciency  vs  out put  cur rent,  SM30-100D

DC in put , Vout = 30 V

fig. 3 - 5

Mea sur ing  rip ple  volt age

WRONG !

fig. 3 - 6

Mea sur ing  rip ple  volt age

RIGHT !

fig. 3 - 7

Pro gram ming  in puts

(in ter nal  cir cuit)

V

A

Imon

0-5V

Vmon

0-5V

Return of

ref, prog, mon.

fig. 3 - 8

Ex ter nal  me ters

us ing  mon i tor  out puts

Summary of Contents for SM120-25D

Page 1: ...rlands www DeltaPowerSupplies com Tel 31 111 413656 SM3000 series PRODUCT MANUAL Contents 1 Datasheet 2 Safety Instructions 3 Descriptions 4 Operating Trouble Shooting Calibration 5 EC Declaration of...

Page 2: ...ution 3 When programming a high voltage unit directly via a PC or via a network connection either ground the negative power output or use a safety isolated interface For more information and schematic...

Page 3: ...d separately to recycle it responsibly to promote the sustainable reuse of material resources 11 Removal of safety covers Safety cover s are used to cover potentially hazardous voltages Observe the fo...

Page 4: ...2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 90 of t...

Page 5: ...programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that the analog inputs and outputs ar...

Page 6: ...gh 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Page 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Page 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Page 9: ...recommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fe...

Page 10: ...ure and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it wil...

Page 11: ...ITER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating swit...

Page 12: ...mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage sour...

Page 13: ...erminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set at t...

Page 14: ...ended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power connecti...

Page 15: ...ON For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units in ser...

Page 16: ...ly to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment An ag...

Page 17: ...nt is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programming can...

Page 18: ...ry to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a short SM...

Page 19: ...h exactly 5 00 V Set output voltage to a low value ensuring the power supply is in CC mode Measure the output current with an accurate shunt Cali brate the current with R686 exactly on the rated max c...

Page 20: ...al EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage fluctuation and flicker EN 61000 6 1 Generic Immunity residential light industrial EN 61000 6 2 Generic Immunity industrial environment...

Reviews: