Description
Notes
Activate Asymmetric LS
Activate asymmetric load share.
Deactivate Asymmetric LS
Deactivate asymmetric load share.
Multi start all sections - this section
See
Multi start all sections
in
Option G5 Power management
.
Fast start sequence from Auto start/ stop via
Digital input 117
See
Fast start of engine
in
Option G5 Power management
.
Fast start sequence from Mains via Power
management
See
Fast start of engine
in
Option G5 Power management
.
Assume all BTB POS fdb OFF in case of pos
fail or ID missing
Faulty handling procedure.
Run all available island DG's
Start all available DG’s in an island power management application.
5.1.2
Mains controller commands
Output, Command
Description
Notes
Lamp test
Activate lamp test (LEDs on display).
Ack. all alarms
Acknowledge all alarms.
Set clock to 4 am
Set the controller clock to 04h00.
Select test type to simple
Test sequence selection.
Select test type to load
Test sequence selection.
Select test type to full
Test sequence selection.
Activate capacity overrule
Activates power capacity overrule.
Deactivate capacity overrule
Deactivates power capacity overrule.
Activate MB parallel
Mains breaker in parallel is activated (parameter 8182).
Deactivate MB parallel
Mains breaker in parallel is deactivated (parameter 8182).
Activate no break transfer
No break transfer is activated.
Deactivate no break transfer
No break transfer is deactivated.
Activate MB close failure start
MB close failure start is activated.
Deactivate MB close failure start
MB close failure start is deactivated.
Inductive reference
Inductive cos phi reference.
Capacitive reference
Capacitive cos phi reference.
Act. power offset [1-3]
Activate the selected power reference offset.
Deact. power offset [1-3]
Deactivate the selected power reference offset.
Act. cos phi offset [1-3]
Activate the cos phi reference offset.
Deact. cos phi offset [1-3]
Deactivate the cos phi reference offset.
Reset horn
Reset the horn relay.
Reset I max. demand
Reset the peak current detected in the controller.
Reset I thermal demand
Reset the thermal current detected in the controller.
Pulse counter [1-2]
Increase the selected pulse counter.
Reset pulse counter [1-2]
Reset the selected pulse counter.
Mains sync. inhibit activate
Activates the close inhibit functionality on the mains breaker.
Application note 4189341276B EN
Page 36 of 50