Output, Command Engine
Description
Notes
Activate Warm Up Ramp
Activate warm up ramp
Battery test
Activate battery test
Eng. heater manual ctrl.
Enable/disable the engine heater function.
Auto start/stop
ON = Start, OFF = Stop.
Remote start
Pulse signal.
Remote stop
Pulse signal.
Start and close GB
Start engine and close generator breaker.
GB open and stop
Open generator breaker and stop engine.
Output, Command Breakers
Description
Notes
GB close inhibit
Prevents the generator breaker from closing.
Open GB
Open the generator breaker.
Close GB
Close the generator breaker.
Open MB
Open the mains breaker.
Close MB
Close the mains breaker.
MB close inhibit
Prevents mains breaker from closing.
Output, Command Plant
Description
Notes
Select application [1-4]
Power management: Select the power management application from the
controller.
Output, Command Power management
Description
Notes
Set to local start
Select local start in a power management application.
Set to remote start
Select remote start in a power management application.
Update mode local
The running mode for the local controller in the power management system is
updated to the selected mode.
Update mode on all
The running mode for all controllers in the power management system is updated
to the selected mode.
Store common settings
See
Handling settings for sections
in
Option G5
.
Abs. prio. handling
Absolute (fixed) start priority.
Rel. prio. handling
Relative (running timer based) start priority.
Activate base load
Activates the base load function.
Deactivate base load
Disables the base load function.
Activate N+X extra DGs
Start and connect extra gensets based on the largest running genset (secured
mode). See
Option G5
for more information.
Deactivate N+X extra DGs
N+X mode is deactivated.
First priority
Forces this controller to have the first priority in a power management system.
Use Ana LS instead of CAN
Forces the power management system to use the analogue load share line.
Application note 4189341276B EN
Page 35 of 50