4.3
Events
4.3.1
Genset controller events
Events, Events
Description
Notes
Mains fail
Mains failure condition.
Peak shaving active
Peak shaving cuts the peak of the mains consumption by paralleling the generator
to the mains.
G volt/freq OK delay expired
Diesel generator V/Hz OK.
Access lock
Binary input access lock activated.
Lamp test
Lamp test in progress.
Battery test active
Battery test in progress.
Mains U OK timer has expired
The timer for mains voltage OK has expired.
Mains F OK timer has expired
The timer for mains frequency OK has expired.
Test type simple selected
Selection of test type: Simple test.
Test type load selected
Selection of test type: Load test.
Test type full selected
Selection of test type: Full test.
BB voltage OK
Busbar voltage.
G volt/freq OK
Generator frequency and voltage are within range.
Ack. all alarms active
Acknowledge all active alarms.
Mode shift activated
Mode shift between a running mode and AMF (Automatic Mains Failure) activated.
Mode shift deactivated
Mode shift between a running mode and AMF (Automatic Mains Failure)
deactivated.
GOV up activated
Speed governor increase activated.
GOV down activated
Speed governor decrease activated.
AVR up activated
AVR (voltage control) increase activated.
AVR down activated
AVR (voltage control) decrease activated.
CBE activated
Activate Close Before Excitation function.
CBE deactivated
Deactivate Close Before Excitation function.
Inductive reference selected
Inductive cos phi reference.
Capacitive reference selected
Capacitive cos phi reference.
Dynamic sync selected
Dynamic synchronisation method selected.
Static sync selected
Static synchronisation method selected.
Power offset [1-3] activated
Power reference offset activated.
Cos phi offset [1-3] activated
Cos phi reference offset activated.
Analogue offset set [1-4] active
The analogue offset set follow the activated nominal settings (1, 2, 3 and 4).
Mains sync. inhibit activated
The mains breaker sync. inhibit function is activated (this does not necessarily
inhibit the synchronisation of the mains breaker).
Mains sync. inhibited
The mains breaker is in fact inhibited.
Max ventilation activated
True when maximum ventilation is activated.
Max ventilation deactivated
True when maximum ventilation is deactivated.
Ethernet ready
Ethernet is ready for read/write.
Application note 4189341276B EN
Page 17 of 50