51
6.11.1
Control panel settings
The dialog is used to set general parameters and functions of the control panel.
Figure 41 Control panel settings
Dialog item
Description
User
Service
Device name
Control panel description
External temperature sensor
External control panel temperature sensor - enable / set
UPS
UPS power supply - enable / set
SD card
Enables the use of an SD card to store the history of values. If
the function is disabled, the history is stored in the internal
RAM (only a few hours / reset clears the history).
When using an SD card, the history is stored approximately 1
year back.
Sort channels by error condition
Channel sorting method (by status / by channel number) on the
main screen.
Negative temperature display
Displaying a negative channel value. Some transmitters send a
negative concentration value (e.g. in case of incorrect zero
calibration), the control panel ignores the negative value and
displays only 0. The setting can also enable the display of
negative values sent by the transmitter.
Syslog
Viewing the system log
Time setting
Control panel time setting
Change Password
Dialog for changing the password of the logged in user
Format SD
Reformats the SD card with the FAT32 file system - clears the
history of values / events
Password reset
Reset all users' passwords to default values
Control panel reset
Performs a device reset
Table 18 Control panel settings