List of status information:
Item name
Description
Type
Transmitter / device type name
Interface
The name of the interface to which the transmitter is connected
Serial number
Transmitter serial number
Gas type
Detection of detected gas (chemical symbol)
Address
Transmitter address on the bus
FW version
Transmitter firmware version
Value
Current measured value
Last calibration
Date of last transmitter calibration
The following calibration
Transmitter calibration validity date. When the calibration expires, a CAL alarm is
activated on the transmitter (calibration)
Active alarms
The list of active transmitter alarms. The individual alarms in the report are
separated by a comma. Example 'A1, CAL' indicates active ALARM1 and calibration
alarm. Only the alarm with the highest priority is displayed on the main channel
element, all active alarms are listed here.
Error condition
Text description of the transmitter error status
Sensor temperature
The temperature read from a transmitter sensor
CPU temperature
The temperature measured on the transmitter processor (internal temperature of
the device)
Hours
Time in hours measured since the last calibration
Alarm1
The set value for alarm1 in the transmitter. The units of value are the same as the
units of the measured quantity.
Alarm2
The set value for alarm2 in the transmitter. The units of value are the same as the
units of the measured quantity.
Alarm3
The set value for alarm3 in the transmitter. The units of value are the same as the
units of the measured quantity.
Alarm4
The set value for alarm4 in the transmitter. The units of value are the same as the
units of the measured quantity.
Offset
The set value for alarm offset in the transmitter. Used for oxygen and PH probe.
The units of value are the same as the units of the measured quantity.
When using offset, the alarm is evaluated according to:
Abs (value - offset) > ALARMx
I.e. when using the offset parameter, an alarm will occur both if the value of the
measured quantity is too high and if it is too low -> the size of the difference
between the measured value and the entered offset is evaluated.
Dead zone
The set value for the transmitter dead band. Defines the value of the measured
quantity below which the zero value will be displayed. The units of value are the
same as the units of the measured quantity.
Table 12 Channel status information