Fictitious concentration test
The fictitious concentration test is used to test the control panel settings and verify the correct response to alarms from
transmitters. When setting a fictitious concentration, the control panel behaves as if the given transmitter was measured by
the transmitter itself. The response to the alarm corresponds to the channel configuration, the alarm is stored in the logs, etc.
The forced concentration remains applied even after leaving the dialog, the user can check the status of the control panel in
the other screens.
Figure 59 Fictitious concentration test
Dialog item
Description
Channel icon
Touching the icon selects a channel in the list for which a fictitious concentration
can be 'forced'. Channels with a forced concentration contain a lock icon.
Fictitious concentration - slider
Slider for quick adjustment of the fictitious concentration of the marked channel.
Fictitious concentration - editbox
Editbox allows you to enter the exact value of the fictitious concentration of the
selected channel.
Reset button
Restores normal channel operation.
Table 33 Dialogue test of fictitious concentration
Tip: After the set time has elapsed, the normal function of the channel will be restored automatically.