Z
Do not connect anything to the terminal block.
E
Connect the DHW sensor (Package AD212).
R
Connect a safety thermostat if the heating circuit is for
underfloor heating.
4
Remove the bridge.
4
Connect the wires from the safety thermostat to the
connector.
T
Connect the outside temperature sensor.
Y
Connect the DHW tank anode.
CAUTION
4
If the tank is fitted with a Titan Active
System® impressed current anode,
connect the anode to the inlet (+ TA on the
anode, - on the tank).
4
If the tank is not fitted with an impressed
current anode, put the simulation
connector in place (delivered with the DHW
sensor - package AD212).
U
Connect the load pump.
Settings to be made for this type of installation
Parameters
Access
Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM
menu
EXTENDED
If a domestic hot water looping pump
is connected to
M
A
on the terminal
block:
O.PUMP A
(1)
Installer level
#SYSTEM
menu
DHW LOOP
"Setting the parameters specific
to the installation", page 102
If safety thermostat is connected to
BL
on the connection terminal block:
IN.BL
Installer level
#PRIMARY INSTAL.P
menu
TOTAL STOP
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
AFC 18 - AFC 24 - AFC 30
5. Installation
09/07/2015 - 300026439-07
69