3.1.4.
Factory test
Before leaving the factory, each boiler is set for optimum performance
and tested to check the following items:
4
Electrical safety
4
Adjustment (CO
2
)
4
Water tightness
4
Oil tightness
4
Checked the tightness of the combusted gas outlet and air inlet
4
Parameter settings.
On commissioning, the installer is responsible for checking
the items mentioned above and, where necessary,
correcting them.
3.2
Technical specifications
3.2.1.
Boiler specifications
Test conditions:
4
CO
2
of 12% at min output and 13% at max output with oil.
4
Maximum operating pressure - Primary circuit (heating water):
3 bar (0.3 MPa)
4
Maximum operating temperature: 85 °C
4
Boiler temperature: Adjustable from 30 to 90 °C
4
Safety thermostat: 105 °C
4
Min flow temperature: 20°C
4
Min. return temperature : 20°C
4
Ambient temperature: 20 °C
Boiler
AFC 18
AFC 24
AFC 30
Minimum
power
Full
power
Minimum
power
Full
power
Minimum
power
Full
power
Power input (Hi)
kW
10.4
17.6
13.9
23.5
17.4
29.4
Nominal output (Pn) at 40/30°C
kW
10.7
18.2
14.3
24.3
17.8
30.3
Nominal output (Pn) at 50/30°C
kW
10.6
18
14.1
24
17.6
30
Nominal output (Pn) at 80/60°C
kW
10
17.1
13.4
22.8
16.7
28.6
(1) These values are pertinent for flexible flue gas evacuation systems with a diameter of 80 mm (rigid ducts). The length of rigid flue gas
evacuation systems is restricted to 18 metres for technical reasons relating to start-up.
(2) 1 mbar = 10 mmWG = 100 Pa
3. Technical specifications
AFC 18 - AFC 24 - AFC 30
12
09/07/2015 - 300026439-07