The installation must be constructed in accordance with prevailing
technical regulations. Depending on prevailing regulations, it is
possible to use a neutralisation station to bring the pH down to a value
of more than 6,5.
1. Mount a standard drainage pipe, DN 32 or more, leading to the
mains drainage system.
2. Connect the condensates discharge pipe with a gradient sufficient
to ensure flow through the siphon to the wastewater network.
3. Mount a trap or a siphon in the discharge pipe.
CAUTION
Do not make a permanent rigid connection owing to
maintenance work on the condensate trap.
4
The condensate drain must be connected openly to
the drain.
4
Set the discharge pipe at a gradient of at least 30 mm
per metre, maximum horizontal length 5 metres.
4
Do not drain condensation water into a roof gutter at
any time.
4
Connect the condensate discharge pipe in
accordance with prevailing standards.
2
C003281-D
pH > 6,5
1
AFC 18 - AFC 24 - AFC 30
5. Installation
09/07/2015 - 300026439-07