n
ANTICIP.A, ANTICIP.B, ANTICIP.C
A
Room temperature setpoint - Comfort
Z
Room temperature setpoint - Reduced
E
Time schedule
R
Anticipation time = Accelerated reheating phase
The anticipation function calculates the heating restart time to reach
the desired room temperature less 0.5 K at the time programmed for
switching to comfort mode.
The start time of the timed programmed corresponds to the end of the
accelerated reheating phase.
The function is activated by setting a different
OFF
value.
The value set corresponds to the time considered necessary to bring
the installation to the required temperature (at outside temperature
0°C), starting from a residual room temperature corresponding to the
reduced temperature setpoint.
Anticipation is optimized if a room sensor is connected.
The regulator will automatically fine set the anticipation time.
This function is dependent on the surplus power available
in the installation.
n
SCREED DRYING
Used to force a constant flow temperature or a train to accelerate
screed drying on underfloor heating.
The setting for these temperatures must follow the screed-layer’s
recommendations.
The activation of this parameter (setting other than
OFF
) forces the
permanent display of
SCREED DRYING
and deactivates all other
functions on the control unit.
When floor drying is active on a circuit, all other circuits (e.g. DHW)
are shut down. The use of this function is only possible on circuits B
and C.
A
STOP DRYING TEMP
Z
START DRYING TEMP
E
Today
R
NB DAYS DRYING
T
Normal regulation (End of drying)
Y
Heating temperature setting (°C)
0,5K
8801N033
1
4
2
3
2
3
4
1
6
5
C
0
0
2
7
6
8
-A
00:00
00:00
00:00
AFC 18 - AFC 24 - AFC 30
6. Commissioning
09/07/2015 - 300026439-07
119