6.7.3.
Professional settings
1. Access the installer level: Press key
-
for around 5 seconds.
2. Set the following parameters:
4
Turn the rotary button to scroll through the menus or
modify a value.
4
Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 97.
Installer level - #PRIMARY LIMITS menu
Parameter
Adjustment range Description
Factory setting Customer setting
BOILER MAX
20 to 90 °C
Maximum boiler temperature
80 °C
MAX.R.HEAT
(1)
0-100%
Maximum boiler output during heating 100%
MAX.DHW
0-100%
Maximum domestic hot water output
100%
MIN.PUMP SPEED
(1)
20-100%
Minimum pump speed
40 %
MAX.PUMP SPEED
(1)
20-100%
Maximum pump speed
100 %
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
Installer level - #SECONDARY LIMITS menu
Parameter
Adjustment range Description
Factory setting
MAX.CIRC.A
30 to 95 °C
Maximum temperature (Circuit A)
75 °C
MAX.CIRC.B
20 to 95 °C
Maximum temperature (Circuit B)
50 °C
MAX.CIRC.C
20 to 95 °C
Maximum temperature (Circuit C)
50 °C
OUT.ANTIFREEZE OFF
, -8 to +10 °C
Outside temperature at which the installation’s antifreeze protection
is activated.
Below this temperature the pumps are permanently on and the
minimum temperatures for each circuit are respected.
When
NIGHT : STOP
is set, the reduced temperature is maintained
in each circuit (
#SECONDARY INSTAL.P
menu).
OFF
: Antifreeze protection is not activated
+3 °C
HCZP D A
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Daytime mode (Circuit A)
OFF
HCZP N A
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Nighttime mode (Circuit A)
OFF
HCZP D B
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Daytime mode (Circuit B)
OFF
HCZP N B
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Nighttime mode (Circuit B)
OFF
HCZP D C
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Daytime mode (Circuit C)
OFF
HCZP N C
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Nighttime mode (Circuit C)
OFF
PRIM.TEMP.DHW
50 to 95 °C
Boiler temperature setting if producing domestic hot water
80°C
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
.
1
1
2
2
r
c
STD
(
'
t
v
0
2
4
6
8
10
12
14
16
18
22
24
20
p
b
AUTO
x c
r
j
M
g
m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
6. Commissioning
AFC 18 - AFC 24 - AFC 30
114
09/07/2015 - 300026439-07