7.12. Setting limit outputs
(10., 11., 12., 13. menu item)
Function
The instrument has two (RL2) or four (RL4) limit outputs.
They are identical with each other, and work independently.
Operation: the instrument keeps comparing the displayed
physical value with the (adjustable) limit value. It switches
the output ON or outpot OFF depending whether the
displayed value is higher or lower than the limit value.
Setting the operating
mode
Sequence of operations
1. Enter the menu with the supervisor code.
The way the code should be type in can be found in
Chapter
7.1. Typing the code in
. You see on the display:
.
2. Keep stepping by pressing the
▲
button as long as you
see this menu item:
(
L
imit
1
).
3. Enter the menu item by pressing the
ENTER
button.
4. 4. You see this:
on the display.
L1 (
L
imit 1) means: limit output No. 1.
Blinking SEt (
Set
tings) means: settings. Here you can
define the operating mode for the limit output. Enter by
pressing the
ENTER
button.
5. Keep stepping by pressing the
▲
button you can select
the desired limit-output operating mode.
•
: the output is always in switched off condition.
[default factory setting]
•
: (
High
). The output gets switched on, when the
displayed physical value is higher than or equal with the low
limit value (L.LI).
•
: (
Low
) The output gets switched on, when the
displayed physical value is lower than the low limit value
(L.LI).
•
: (
Insid
e) The output gets switched on, when the
displayed physical value is between the low limit value (L.LI)
and the higher limit value (H.LI).
Summary of Contents for DT1400 RL2 IA
Page 1: ...DT1400 xx xx Limit switch Operating Instructions ...
Page 68: ...DT1400 xx xx 68 20170920 V0 10 2 Application example Analog output option ...
Page 69: ...DT1400 xx xx 20170920 V0 69 RL4 option ...
Page 70: ...DT1400 xx xx 70 20170920 V0 TS option ...
Page 71: ...DT1400 xx xx 20170920 V0 71 ...
Page 72: ......