DATAKOM DKG-705 User’s Manual
705_USER.doc
- 32 -
13. BUILT-IN EXERCISER
The unit offers automatic exerciser operation. The exercise operation may be done on a daily,
weekly or monthly basis.
The start day and time of the exercise is programmable as well as its duration. The exercise may
be done with or without load following programming.
The program parameters related to the exerciser are:
P_635:
Exercise start day and hour
P_636:
Exercise duration
P_637:
Exercise off-load / on load
P_638:
Daily / Weekly / Monthly Exercise
Please refer to the programming section for a more detailed description of the above parameters.
When the start day and hour of exercise has come, the unit will automatically switch to either
TEST
or
LOAD TEST
mode. The engine will run and if the on load exercise is selected then the load will be
transferred to the genset.
If a mains failure occurs during the off-load exercise, the load will not be transferred to the genset
unless the
Emergency Backup Operation
is allowed by setting the parameter
P_629
to 1. Thus it is
highly recommended that the Emergency Backup mode enabled with off-load exerciser.
At the end of the exercise duration, the unit will switch back to the initial mode of operation.
If any of the mode selection keys are pressed during exercise, then the exercise will be ended.
Using the daily exercise mode, the unit may feed the load from the genset during predefined hours
of the day. This operation may be used in high tariff periods of the day.