DATAKOM DKG-705 User’s Manual
705_USER.doc
- 31 -
12. WEEKLY OPERATION SCHEDULE
In AUTO mode, the unit offers the capability of defining a weekly schedule of operation.
The unit has 8 programmable turn-on/turn-off time pairs. These programmable parameters allow
the genset to operate automatically only in allowed time limits.
In most applications, the genset is requested to operate only in working hours. Thanks to the
weekly program feature unwanted operation may be prohibited.
The weekly operation schedule is
only active in AUTO
mode. In other modes it will not affect the
genset operation.
In AUTO mode, if the operation of the genset is disabled by the weekly schedule, then the AUTO
led will flash (instead of a steady on state).
Each turn-on/turn-off time is defined in 15 minute steps. These parameters are defined in the
program group_4, parameters 400 to 415. An example setup may be as follows:
P_400: Turn on: MO 07:00
P_401: Turn off: MO 18:00
P_402: Turn on: TU 07:00
P_403: Turn off: TU 18:00
P_404: Turn on: WE 07:00
P_405: Turn off: WE 18:00
P_406: Turn on: TH 07:00
P_407: Turn off: TH 18:00
P_408: Turn on: FR 07:00
P_409: Turn off: FR 18:00
P_410: Turn on: SA 07:00
P_411: Turn off: SA 13:00
P_412: Turn on: SA 13:00
P_413: Turn off: SA 13:00
P_414: Turn on: SA 13:00
P_415: Turn off: SA 13:00
If the same time is used in more than one parameter, only the first encountered one is considered.
In the above example, SATURDAY 13:00 will be a
turn-off
time.