DATAKOM DKG-705 User’s Manual
705_USER.doc
- 38 -
Group Parameter Definition
Unit Min Max Description
5
509
Gen. Contactor Timer
Sec 0.5 120 This is the period after the mains
contactor has been deactivated and
before the generator contactor has been
activated.
5
510
Overcurrent Limit
Amp 20 5000 If the current is over this limit, an
Alternator Overcurrent alarm
will be
generated after the
Overcurrent Timer
(P511)
period.
5
511
Overcurrent Timer /
Excess Power Timer
Sec
1
20 This is the period between the current
goes over the
Overcurrent Limit (P510)
and the
Alternator Overcurrent alarm
occurs.
This is also the period between the genset
power goes over the
Excess Power
Load Dump Limit (P617)
and the
Gen
Excess Power Load Dump
occurs.
5
512
Mains Low Limit
Volt
0
240
AUTO
TEST
5
513
Mains High Limit
Volt 100 300
AUTO
TEST
5
514
Gen Low Limit
Volt 60
240 If one of the generator phase voltages
goes under this limit when feeding the
load, this will generate a
Genset Low
Voltage Alarm
and the engine will stop.
5
515
Gen High Limit
Volt 100 300 If one of the generator phase voltages
goes over this limit when feeding the load,
this will generate a
Genset High Voltage
Alarm
and the engine will stop.
5
516
Low Freq. Shutdown
Hz
10
60 If the genset frequency goes under this
limit for
Frequency Timer (P520)
period,
this will generate a Genset
Under-
Frequency Alarm
and the engine will
stop.
5
517
Low Freq. Warning
Hz
10
60 If the genset frequency goes under this
limit for
Frequency Timer (P520)
period,
this will generate a
Genset Under-
Frequency Warning
.
5
518
High Freq. Shutdown
Hz
40
150 If the genset frequency goes over this limit
for
Frequency Timer (P520)
period, this
will generate a
Genset Over-
Frequency Alarm
and the engine will
stop.
5
519
High Freq. Warning
Hz
40
150 If the genset frequency goes over this limit
for
Frequency Timer (P520)
period, this
will generate a
Genset Over-Frequency
Warning
.
5
520
Frequency Timer /
Engine rpm Timer
Sec
1
20 This is the period between the genset
frequency or engine rpm goes out of the
limits and an alarm occurs.
5
521
Horn Timer
Sec
0
240 This is the maximum period during which
the alarm relay output may stay active.
If the period is set to 0, this will mean
that the delay is unlimited.