DATAKOM DKG-705 User’s Manual
705_USER.doc
- 15 -
4.2 Load Dump Alarms
Definition
Source
Description
Low Oil Press.Switch
Digital Input
High Eng.Temp.Switch
Digital Input
Emergency Stop
Digital Input
Low Coolant Level
Digital Input
Alternator High Temp. Digital Input
High Oil Temp.
Digital Input
Overload
Digital Input
Low Fuel Level
Digital Input
Battery Charger Fail
Digital Input
Spare Alarm 7
Digital Input
Spare Alarm 6
Digital Input
Spare Alarm 5
Digital Input
Spare Alarm 4
Digital Input
Spare Alarm 3
Digital Input
Spare Alarm 2
Digital Input
Spare Alarm 1
Digital Input
These load dump alarms are set depending on the digital input
settings. The related program parameters are
P_700
to
P_776
.
Gen Reverse Power
Internal
Set if the genset consumes active power (KW) from the mains and
this power goes over the
Reverse Power Load Dump (P_618)
limit.
Gen Excess Power
Internal
Set if the genset power (KW) supplied to the load goes over the
Excess Power Load Dump (P_617)
limit for
Overcurrent / Excess
Power Timer (P_511)
.
Alternator Overcurrent
Internal
Set if at least one of the genset phase currents goes over the
Overcurrent Limit (P_510)
for
Overcurrent / Excess Power
Timer (P_511)
.