DATAKOM DKG-705 User’s Manual
705_USER.doc
- 57 -
Synchronization failure:
Check the parameters
P_A02
,
P_A04
,
P_A15
and
P_A16
. If Dual Genset mode is used then check also
P_A39
and
P_A40
. If one of them is defined too low, this may delay or disable the synchronization
process.
Check the synchronization fail timeout parameter (
P_A07
), if necessary increase. A typical delay may be
20 seconds.
Check the synchronization limits (
P_A10
,
P_A11
,
P_A12
), If necessary widen the limits. A typical
application may be
P_A10=0.5Hz
,
P_A11=5V
,
P_A12=5º