5.2. Remote Start Operation
The unit offers the possibility of
REMOTE START
mode of operation. In this mode the mains
phases are not monitored. If the REMOTE START signal is present then the mains will be supposed to fail,
inversely if the REMOTE START signal is absent, then mains voltages will be supposed to be present. The
front panel mimic diagram’s mains LEDs will reflect the status of the REMOTE START input.
Any of the digital inputs may be programmed as a REMOTE START input. For this the
corresponding input’s
P_7x0
parameter should be set to
23
. The REMOTE START signal may be a NO or NC
contact, switching to either battery positive or battery negative. These selections are made using parameters
P_7x5
and
P_7x6
.