DATAKOM DKG-705 User’s Manual
705_USER.doc
- 44 -
Group Parameter Definition
Unit Min Max Description
6
635
Exercise start day
and hour
-
0
168 This parameter defines the start day and
hour of the exerciser.
Values higher or equal to 168 mean that the
exerciser is off.
The exercise may be selected to start at the
beginning of the any hour of the week. The
parameter value is the hour count of the
start time.
Examples:
0 = exercise starts at Monday 00:00
1 = exercise starts at Monday 01:00
8 = exercise starts at Monday 08:00
24 = exercise starts at Tuesday 00:00
167 = exercise starts at Sunday 23:00
168 = exerciser off
If a daily exercise is selected with
parameter P_638=0, then the day
information is
don’t care
and the exercise
will be performed every day regardless of
the day selection.
If the monthly exercise is selected with
parameter P_638=2 then the exercise will
be performed during the first 7 days of each
month at the programmed day and hour.
6
636
Exercise duration
min. 10 1430 This parameter defines the exercise
duration and programmed in 10 minute
steps up to 24 hours.
6
637
Daily / Weekly /
Monthly Exercise
-
0
2
0:
exercise every day (the exercise will be
performed every day regardless of the day
selection with parameter P_635).
1:
exercise once per week
2:
exercise once per month (the exercise
will be performed during the first 7 days of
each month at the programmed day and
hour).
6
638
Exercise
off_load/on_load
-
0
1
If this parameter is set to 0 the genset will
not feed the load during exercise. If it is set
to 1, then the load will be transferred to the
genset during the exercise.