DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 59 -
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(2)
Low rpm Shutdown
rpm
0
If the engine speed goes under this limit, a
GENSET
LOW SPEED
alarm is generated and the engine stops.
(2)
Low rpm Warning
rpm
0
If the engine speed goes under this limit, a
GENSET
LOW SPEED
warning is generated.
(2)
High rpm Warning
rpm
2200
If the engine speed goes over this limit, a
GENSET
HIGH SPEED
warning is generated.
(2)
High rpm Shutdown
rpm
2400
If the engine speed goes over this limit, a
GENSET
HIGH SPEED
alarm is generated and the engine
stops.
(2)
Fan turn-on temp
°C
90
If the coolant temp is above this limit then the fan relay
function will become active.
(2)
Fan turn-off temp
°C
80
If the coolant temp is below this limit then the fan relay
function will become inactive.
(2)
High Oil Temperature
Warning
°C
100
If the oil temperature measured from the analog input
goes over this limit, this will generate a HIGH
OILTEMPERATURE SENDER warning.
(2)
High Oil Temperature
Shutdown
°C
120
f the oil temperature measured from the analog input
goes over this limit, this will generate a HIGH OIL
TEMPERATURE SENDER alarm and the engine will
stop.
(2)
Oil Temp. Sender Type
-
1
This parameter selects the oil temperature sender type:
0: The sender characteristics are defined in Sender
Characteristics table.
1: VDO
2: DATCON DAH type
3: DATCON DAL type
(2)
Speed up/down pulse
minimum duration
msec
50
If the engine speed is controlled through up/down
relays, this parameter defines the minimum pulse
duration.
(2)
Speed up/down pulse
maximum duration
msec
250
If the engine speed is controlled through up/down
relays, this parameter defines the maximum pulse
duration.
(2)
Speed up/down pulse
delay
msec
20
This is the minimum delay between 2 successive
speed up/down pulses.
15.3. ENGINE PARAMETERS GROUP (continued)