DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 85 -
ADDRESS
(hex)
R /
W
DATA
SIZE
COEFFICIENT DESCRIPTION
0037
R
8bit
-
Warning bits
bit_0: service request warning
bit_2:low engine battery voltage fail
bit_3: high engine battery voltage warning
bit_4: charge fail warning
bit_5: ECU fail warning
0038
R
16bit
-
Warning bits
bit_0: genset low voltage warning
bit_1: genset high voltage warning
bit_2:reverse power warning
bit_3: high oil temp sender warning
bit_4: high canopy temp sender warning
bit_8: oil pressure sender fail warning
bit_9: temperature sender fail warning
bit_10: fuel level sender fail warning
bit_11: oil temp sender fail warning
bit_12: canopy temp sender fail warning
0039
R
8bit
-
Relay output statuses
bit_0: load contactor
bit_1: crank relay
bit_2: spare_2
bit_3: spare_1
bit_5: fuel
003A
R
16bit
-
Relay extension module, relay statuses
bit_0: module_1, relay_1 status
bit_1: module_1, relay_2 status
bit_2: module_1, relay_3 status
bit_3: module_1, relay_4 status
bit_4: module_1, relay_5 status
bit_5: module_1, relay_6 status
bit_6: module_1, relay_7 status
bit_7: module_1, relay_8 status
bit_8: module_2, relay_1 status
bit_9: module_2, relay_2 status
bit_10: module_2, relay_3 status
bit_11: module_2, relay_4 status
bit_12: module_2, relay_5 status
bit_13: module_2, relay_6 status
bit_14: module_2, relay_7 status
bit_15: module_2, relay_8 status
003B
R
16bit
-
Relay function statuses
bit_0: fuel
bit_1: alarm
bit_2: crank
bit_3: stop
bit_4: load contactor
bit_6: choke
bit_7: preheat
bit_8: shutdown alarm
bit_9: shutdown or loaddump
bit_10: shutdown or loaddump or warning
bit_11: automatic ready
bit_12: weekly schedule On time
bit_13: exerciser on
bit_14: load dump alarm