DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 20 -
Structure:
CANBUS, non isolated.
Connection:
3 wires (CANH-CANL-GND).
Data rate:
250 kbps
Termination:
Internal 120 ohms provided
Common mode voltage:
-0.5 VDC to +15 VDC, internally clamped by transient suppressors.
Max distance:
200m with 120 ohm balanced cable
Description:
RS-232, non isolated.
Functionality:
External modem, PC connection, PLC
connection
Connector:
RJ11-6pin
Connection:
6 wires (Rx-Tx-DTR-CxD-GND-+10V).
Full duplex.
Baud rate:
9600 bauds
Data type:
8 bit data, no parity, 1 bit stop
Max distance:
15m
Terminal
description:
1: DTR
output
2: Tx output
3: CxD input
4: GND
5: Rx input
6: +10V
Front view of RJ11 6 pin
connector
6 1
3.13. RS-232 PORT (OPTIONAL)
3.12. J1939-CANBUS PORT
RS-232
Connector