OVERLOAD
Set if the alternator output current goes over the
Overcurrent Limit
for
Overload Timer
. If the current goes below the limit before expiration of the
timer then no alarm will be set.
EXCESS POWER
Set if the genset power (KW) supplied to the load goes over the
Excess
Power
limit for
Overload Timer
. If the power goes below the limit before
expiration of the timer then no alarm will be set.
Digital input and analog sender alarms are fully programmable
for the alarm name, sampling and action.
Only internal alarms are explained in this section.