DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 34 -
STOPPING THE ENGINE:
Press STOP
button
STARTING THE ENGINE:
Press RUN
button
MANUAL LOAD TRANSFER:
Press TEST
button. The genset will run and take the load.
LOAD TEST:
Press TEST
button. The genset will run and take the load.
AUTOMATIC OPERATION:
Press AUTO
button.
The STOP mode is entered by pressing the
button.
In this mode, the genset will be in a rest state.
When STOP mode is selected, if the genset is running under load, then it will be immediately unloaded. The
engine will continue to run during
Cooldown Timer
and will stop afterwards.
If the STOP button is pressed again, then the engine will immediately stop.
If the engine fails to stop after the expiration of
Stop Timer
then a
Fail to Stop
warning will occur.
If a
Remote Start
or
Force to Start
signal arrives in STOP mode, the genset will not start until AUTO mode is
selected.
Mode can be changed anytime without negative effect.
Changing the operation mode while the genset is running will
result into a behavior suitable for the new operating mode.
10.2.STOP MODE
10.1. QUICK START GUIDE
10. OPERATION OF THE UNIT