DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 23 -
Term Function
Technical data
Description
12
TEMP MEASUREMENT
INPUT
PT100 sensor input
Connect the battery bank temperature
sensor to these inputs.
The sensor must be of PT100 type.
Polarity is not important.
The sensor will be used to protect the
battery bank from overheating during
charge cycle.
13
TEMP MEASUREMENT
INPUT
14
AC
Output, 10A max
These outputs supply energy to the
electric actuator. The output voltage will
increase in order to supply more fuel to the
engine. A short circuit protection is
provided.
15
ACTUATOR -
16
GROUND
O VDC
Power supply negative connection.
17
BATTERY POSITIVE
+12 or 24VDC
The positive terminal of the DC Supply
shall be connected to this terminal. The
unit operates on both 12V and 24V battery
systems.
18
FUEL LEVEL SENDER
Input, 0-5000 ohms
Analogue fuel level sender connection. Do
not connect the sender to other devices.
The input has programmable ohms for
VDO senders.
19
OIL PRESSURE SENDER
Input, 0-5000 ohms
Analogue oil pressure sender connection.
Do not connect the sender to other
devices. The input has programmable
characteristics and connects to any kind of
sender.
20
COOLANT TEMP. SENDER
Input, 0-5000 ohms
Analogue high temperature sender
connection. Do not connect the sender to
other devices. The input has
programmable characteristics and
connects to any kind of sender.
21
CHARGE
Input and output
Connect the charge alternator’s WL/D+
terminal to this terminal. This terminal will
supply the excitation current and measure
the voltage of the charge alternator.
22
RELAY-2 (HORN RELAY)
Output 1A/28VDC
This output has programmable function,
selectable from a list.
23
RELAY-1 (STOP RELAY)
Output 1A/28VDC
This output has programmable function,
selectable from a list.
24
START RELAY
Output 1A/28VDC
This output controls the engine cranking.
25
FUEL RELAY
Output 1A/28VDC
This output is used for fuel solenoid
control.