DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 14 -
Measurement method:
Isolated DC voltage measurement
Sampling rate:
100K s/s
Input voltage range:
0 to 70 VDC
Measurement range:
0 to 70VDC
Input impedance:
215 K-ohms
Display resolution:
0.1VDC
Isolation:
500VAC, 1minute
Accuracy:
0.5% + 1 digit (±0.35V@50VDC)
Measurement method:
Isolated DC voltage measurement
Sampling rate:
100 Ks/s
Input voltage range:
0 to 100 mVDC
Measurement range:
0 to 100 mVDC
Input impedance:
1000 ohms
Isolation:
500VAC, 1minute
Accuracy:
0.5% + 1 digit (±0.6A@100ADC)
Current shunt range:
1A/60mV to 5000A/60mV
Display resolution:
0.1ADC (shunt < 250A/60mV)
1ADC (shunt > 250A/60mV)
Be careful about not to applying more than 100mVDC,
otherwise the unit may get damaged.
3.3. BATTERY BANK CHARGE CURRENT INPUT
3.2. BATTERY BANK DC VOLTAGE INPUTS