05725-02-0499 <90-00201>
P
AGE
35
Verify that the RCV DATA LED is flashing on the 49029. If it is
not, check the 46033 E-System adapter in slot 8 by removing the
fuse for slot 8 (Fuse 8) and removing the E-System adapter. Check
the switch setting per Tables E and F in this manual. If the
switch settings are correct, reinstall the module and the fuse.
If the RCV DATA LED on the 49029 subassembly on the MAP still
does not flash, remove the fuse again and replace the E-System
adapter with a known good module after setting its switch settings
per Tables E and F. Replace the fuse for slot 8.
If the 49029 subassembly XMT DATA LED on the MAP does not
flash, remove the fuse for slot 7 (Fuse 7) and verify that the switch
settings are correct by comparing them with Tables H through L.
Verify that the strap settings on the 49029 module are correct; per
the settings in Table M.
Replace the module and the fuse. If the RCV LED on the 49029
module flashes, and the switch settings are correct, and the XMT
LED still does not flash, replace the MAP, with a 49029 subassem-
bly on it, with a known good one that has the switches set cor-
rectly per the Tables.
Changing Default Alarm Levels
All alarms default to a D level. If it is necessary to change any
point to another alarm level, use the craft port of the MAP (C6-A)
and attach a laptop, in a terminal mode (VT100), or a dumb
terminal and set that terminal for a baud rate of 9600 baud, 8 bit
word, one stop bit and 0 parity bits.
Changing the levels of any alarm from the default level is done by
using the craft printer port.
1.
When a laptop or dumb terminal is connected to the craft port of the
MAP, and the MAP is reset, a > character will be seen on the
screen, indicating that the MAP is communicating with the terminal
device.
2.
Type in the command
UNLOCK
and hit the
ENTER
key. If there
has been no password entered into the system, the message System
Unlocked will come back to the user.
NOTE:
If a password has been entered, you will have to enter the
password, and then the message.System Unlocked will come
back
3.
To set the levels of alarms for each MAT address, type in:
MAT
[MAT address]
OPT
[option letters]
Assign all 16 points and put a space between each letter (point assign-
ment)
CONTINUED
. . .
TURN-UP PROCEDURE