Purpose:
Changes the characteristics of an individual alarm point.
Format:
SET ID # DISPLAY # POINT # GLOBAL CRITICAL.
SET ID # DISPLAY # POINT # LOCAL CRITICAL.
SET ID # DISPLAY # POINT # GLOBAL MAJOR.
SET ID # DISPLAY # POINT # LOCAL MAJOR.
SET ID # DISPLAY # POINT # GLOBAL MINOR.
SET ID # DISPLAY # POINT # LOCAL MINOR.
SET ID # DISPLAY # POINT # GLOBAL STATUS.
SET ID # DISPLAY # POINT # LOCAL STATUS.
Remarks:
When an alarm point is defined or redefined, the changes are
written to the database in nonvolatile memory along with all
other system configuration information.
The following abbreviations can be used:
USE...
DISP
PNT or P
GLOB
LOC
CRIT or A
MAJ or B
MIN or C
STAT
IN PLACE OF...
DISPLAY
POINT
GLOBAL
LOCAL
CRITICAL
MAJOR
MINOR
STATUS
The symbol # can be an individual device, it can be a group of
devices, or it can be the term ALL, meaning all devices. ID # can
be any or all addresses from 1 through 32.
DISP # can be any or all displays from 1 through 64 (and GPP’s
internal displays 65-73).
PNT # can be any or all points from 1 through 64.
Input Example:
SET ID 11 DISP 25 PNT 55 CRIT
PRINTER SYNTAX